3Com 8800 manual ENGINEERING, Maintenance Troubleshooting, LED Indication

Page 21

ENGINEERING, MAINTENANCE AND

5 TROUBLESHOOTING

Maintenance and

This section provides field maintenance information and troubleshooting procedures

Troubleshooting

for the PoE Power Rack and power supply modules. Review the safety information in

 

section 3 of this manual before performing maintenance procedures

 

All procedures described in this section must be performed by qualified maintenance

 

personnel only.

 

The power supply modules are not field serviceable and must be replaced in the event

 

of a failure.

 

 

LED Indication

Use Table 6 to determine if there is a fault with PoE Power Rack.

 

When visual indicators do not identify a defective part, notify your authorized service

 

representative.

 

Table 6 Troubleshooting Guide

Controller alarm

Power supply

 

 

 

 

module

 

 

 

 

status

display

Possible problems

Possible solution

 

 

 

 

 

 

RUNALM

NONE

The AC power input

1

Verify that AC

 

 

 

circuit breakers has

 

power input

 

 

 

opened.

 

circuit breaker is

 

 

AC input voltage is too

 

closed; close

 

 

 

circuit breaker if

 

 

 

low or power is lost

 

 

 

 

 

it is open.

 

 

 

 

 

 

 

 

 

2

Verify the AC

 

 

 

 

 

power is present

 

 

 

 

 

and in normal

 

 

 

 

 

range.

RUNALM

AC OKFAULT

Power supply module

Replace the power

 

 

 

failure

supply module

 

 

Output beyond normal

 

 

 

 

 

range

 

 

RUNALM

AC OKDC

Communication error

Replace the power

 

OKFAULT

between the power supply

supply module

 

 

module and the controller

 

 

RUNALM

AC OK

Power supply module has

1

Initialize the

 

 

 

no output and it is in

 

power supply

 

 

 

standby mode

 

module or reset

 

 

Over load

 

the controller.

 

 

2 Check if the load

 

 

Ambient temperature is

 

 

 

is over the

 

 

 

too high

 

 

 

 

 

rating.

 

 

 

Power supply module

 

 

 

3

Check the

 

 

 

failure;

 

 

 

 

ambient

 

 

 

 

 

 

 

 

 

 

temperature.

 

 

 

 

4

Replace the

 

 

 

 

 

power supply

 

 

 

 

 

module

Image 21
Contents 3Com Switch Power Over Ethernet United States Government Legend 3Com Corporation Campus Drive Marlborough, MA USAContents Contents Introduction PoE Power Rack Rear View Architecture and Configurations Introduction PoE Power Rack Power SupplySystem Description OverviewVisual indicators Power Supply ModuleSystem Controller Descriptions, colors, and functions are shown in TablePin Definition RS485 and RS232 signals are described in and TableRefer to Figure Distribution PanelSafety Safety StatementsSafety Symbols Safety Introduction Installation and TestingGuidelines EMI ConsiderationsNumber Model Ports Type Disconnect Detection Module Technical SpecificationsRemoving Power Supply Module and Dummy Faceplate Frame Grounding Powering on the Device Installation and Testing Maintenance ENGINEERING, Maintenance TroubleshootingTroubleshooting LED IndicationENGINEERING, Maintenance and Troubleshooting