RTS KGATX0101400 Connecting Start Circuit Wires, Auxiliary Contacts, Functional Tests Adjustments

Page 6

Section 3 — Operation

RTS “W” Type Transfer Switch

NOTE:

Use a torque wrench to tighten the conductors, being sure not to overtighten, or damage to the switch base could occur. If undertightened, a loose connection would result, causing excess heat which could damage the switch base.

Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol- lows

1.Connect UTILITY (NORMAL) power source cables to switch terminals N1, N2, (N3).

2.Connect EMERGENCY (STANDBY) source power cables to transfer switch terminals E1, E2, (E3).

3.Connect customer LOAD leads to switch termi- nals T1, T2, (T3).

4.Connect neutral conductors of UTILITY, EMERGENCY and customer LOAD to the neutral block.

Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes.

Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits.

Auxiliary Contacts are rated 10 amps at 125 or 250 volts AC. DO NOT EXCEED THE RATED VOLTAGE AND CURRENT OF THE CONTACTS.

Figure 2.3 – Auxiliary Contacts

Side views shown in Utility position

2.5CONNECTING START CIRCUIT

WIRES

Control system interconnections consist of UTILITY 1 and 2, and leads 23 and 194. Control system interconnection leads must be run in a conduit that is separate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:

 

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

 

 

 

SIZE

 

 

460 feet (140m)

No. 18 AWG.

 

 

461 to 730 feet (223m)

No. 16 AWG.

 

 

731 to 1,160 feet (354m)

No. 14 AWG.

 

 

1,161 to 1,850 feet (565m)

No. 12 AWG.

 

 

 

 

 

2.6AUXILIARY CONTACTS

If desired, there are Auxiliary Contacts on the transfer switch to operate customer accessories, remote advi- sory lights, or remote annunciator devices. A suitable power source must be connected to the COMMON (C) terminal. See Figure 2.3.

Contact operation is shown in the following chart:

 

 

Switch Position

 

 

 

Utility

Standby

 

 

Common to Normally Open

Open

Closed

 

 

Common to Normally Closed

Closed

Open

 

 

 

 

 

 

 

4

 

 

 

3.1FUNCTIONAL TESTS AND

ADJUSTMENTS

Following transfer switch installation and intercon- nection, inspect the entire installation carefully. A competent, qualified electrician should inspect it. The installation should comply strictly with all appli- cable codes, standards, and regulations. When abso- lutely certain the installation is proper and correct, complete a functional test of the system.

Perform functional tests in the exact order pre- sented in this manual, or damage to the switch could be done.

IMPORTANT: Before proceeding with functional tests, read and make sure you understand all instructions and information in this section. Also read the infor- mation and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation.

Image 6
Contents Technical Manual  General Hazards  Back Cover Safe USE of Transfer Switch Transfer Switch Data LabelTransfer Switch Enclosure IntroductionUnpacking Introduction to InstallationConnecting Power Source and Load Lines MountingConnecting Start Circuit Wires Functional Tests AdjustmentsAuxiliary Contacts Manual Operation ‹ 3.2.1 Close to Normal Source SideVoltage Checks ‹ 3.2.2 Close to Emergency Source SideGenerator Tests Under Load Installation Diagram Electrical Data GTS GTS Exploded Views and Parts List QTY Description Carrier WARRANTY/SERVICE