INSTALLATION INSTRUCTIONS PN79G
CABLE REQUIREMENT: Terminates most
IWC wire with a .050" (1.27mm) max. o.d., either PVC or Plenum rated.
5.To help contain
Attach horizontal cable manager trough to towers and vertical cable managers using #12 sheet metal screws and #12 external tooth lockwashers (provided). Fasten securely to assure grounding. Attach ground lug
|
|
|
| Component Quantity per Tower System |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| Base | Trough |
| Connecting Blocks |
| Label Holders | Labels | |||
|
|
|
|
|
|
|
|
|
| |
Part Number | P110B100 | P110JT | P110CB3 | P110CB4 | P110CB5 | P110CB4IG | P110CB5IG | P110LH | DSL110 | |
|
|
|
|
|
|
|
|
|
|
|
P110KT3004 | 3 | 3 | - | 60 | 12 | - |
| - | 6 | 6 |
|
|
|
|
|
|
|
|
|
|
|
P110KT3005 | 3 | 3 | - | - | 60 | - |
| - | 6 | 6 |
|
|
|
|
|
|
|
|
|
|
|
P110KT9004 | 9 | 9 | - | 180 | 36 | - |
| - | 18 | 18 |
|
|
|
|
|
|
|
|
|
|
|
P110KT9005 | 9 | 9 | - | - | 180 | - |
| - | 18 | 18 |
|
|
|
|
|
|
|
|
|
|
|
INSTALLATION TIPS:
1.
2.Never install wire into a slot previously used for a larger gauge.
3.Be careful to strip back cable jacket only as required for termination.
4.Use care to maintain pair twists to within 0.5" (13mm) of the termination strip.
5.When stripping cable jacket, be careful not to cut the insulation on the individual wires.
6.Avoid sharp bends when routing cable.
As with all Wiring Accessories, the following statements apply:
1.Never install communications wiring during a lightning storm.
2.Never install communications wiring in wet locations unless the product is specifically designed for use in wet locations.
3.Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface.
4.Use caution when installing or modifying communication wiring.