Page 22

INTEGRATING THE UPS

5.Run profiler from the command prompt or double-click profiler.exe from Microsoft Windows Explorer.

By default, Modbus Profiler uses the communication port specified in the [Connection] section of the profiler.ini file. If profiler fails to connect using this communication port, you are prompted with a list of alternate communication ports. You may also edit the Port= value in the [Connection] section of the profiler.ini file to change the default value.

6.Modbus Profiler creates an output file named profiler.csv in the directory where the Modbus Profiler tool is located.

Before the program exits, you are prompted to view the data.

The comma delimited file can be easily imported into Microsoft Excel for viewing of the Modbus data. This data is used to create the necessary template files on your Building Management System for polling the desired UPS information.

NOTE Modbus Profiler does not provide Modbus data for the Powerware 9315 Series UPS.

Powerware 9315 configuration-specific profiles are available in the directory where the

Modbus Profiler tool is located (refer to the 950*.pdf files).

Example Modbus Profiler Output Files

The following tables are sample Modbus Profiler output files for a Powerware 9315 Reverse Transfer (RT) Single Module UPS. Refer to the Master Modbus Register Map for a complete list of the Status, Alarm, and Meter data for all Powerware UPS equipment (open the reg_map.pdf file in the directory where the Modbus Profiler tool is located).

Table 4. Read Input Status - Modbus Function Code 02 (Inputs Start at 10000)

Register

Name

Value

Format

Unit

 

 

 

 

 

 

1

 

On Battery

0

BOOL

Status

 

 

 

 

 

 

10

 

On Bypass

1

BOOL

Status

 

 

 

 

 

 

11

 

System Normal

0

BOOL

Status

 

 

 

 

 

 

16

 

UPS Off

0

BOOL

Status

 

 

 

 

 

 

 

 

NOTE Registers 1–16 are mutually exclusive.

 

 

 

 

 

 

 

 

 

112

 

Rectifier Status

1

BOOL

Status

 

 

 

18

EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.com

 

Image 22
Contents Powerware Modbus Card User’s Guide Class a EMC Statements Requesting a Declaration of ConformityTable of Contents Table of Contents Chapter Introduction Ethernet Installing the Modbus Card Inspecting the EquipmentFour-Wire Communication U T I O NModbus Card Jumpers Installing the Modbus Card into an X-Slot Removing the Single-Port ModuleWiring the Modbus Card Two-Wire NetworksFour-Wire Networks RS-485 Terminal StripRS-485 Modbus Port RS-485 Terminal Strip RS-485 Terminal Strip Pin AssignmentsTermination RS-485 DB-9 Pin NumbersBiasing Resistors RS-232 Modbus Port RS-232 DB-9 Pin NumbersModbus Card Configuration Configuring the Modbus CardPress Enter. The Configuration screen appears see Figure Continue to , Integrating the UPS on Modbus Card Configuration Integrating the UPS Generating Modbus DataExample Modbus Profiler Output Files Read Input Status Modbus Function Code 02 Inputs Start atRectifier Input Status Output overload Register Meter Name Scale Unit Inverter Volts Phase C Troubleshooting Problem Possible Cause Corrective ActionModbus Card Default Jumper Settings Service and Support Troubleshooting Page 164201376C

FCC 15 specifications

The Powerware FCC 15 is a robust and versatile power distribution unit designed to meet the increasing demands of modern data centers and enterprise environments. This innovative solution offers unparalleled reliability, efficiency, and scalability, making it suitable for various applications, from small server rooms to larger IT infrastructures.

One of the main features of the Powerware FCC 15 is its modular design. This allows users to easily scale their power distribution capabilities by adding or removing components as necessary, ensuring that the system evolves alongside their growing needs. The FCC 15's modularity brings significant advantages in terms of flexibility and cost efficiency, as organizations can optimize their power infrastructure without making substantial initial investments.

Efficiency is a hallmark of the Powerware FCC 15. It employs advanced technologies such as intelligent power management systems and high-efficiency components. These features not only help in reducing energy consumption but also minimize operating costs. The integrated monitoring capabilities of the FCC 15 allow for real-time tracking of power usage, enabling IT managers to better understand their power consumption patterns and make informed decisions regarding their energy strategies.

Safety is another critical characteristic of the Powerware FCC 15. It includes multiple layers of protection, such as surge protection, overcurrent protection, and voltage regulation, to safeguard sensitive equipment from power disturbances. This focus on safety is vital, as data loss or hardware damage can be significantly costly for businesses.

In addition to safety and efficiency, the Powerware FCC 15 is designed with a user-friendly interface. The LCD touch screen provides easy access to essential data and configuration settings, allowing for straightforward management. This ease of use is complemented by seamless integration with existing IT infrastructures, ensuring that organizations can implement the FCC 15 with minimal disruption.

The Powerware FCC 15 also supports various redundancy options, enhancing system reliability. Features such as N+1 or 2N configurations ensure that power is resilient and continuous, protecting mission-critical systems from failures. Furthermore, the FCC 15 is engineered to be compatible with renewable energy sources, catering to the growing trend of sustainability in power management.

In summary, the Powerware FCC 15 is an advanced power distribution solution characterized by its modularity, efficiency, safety features, user-friendly interface, and reliability. As businesses increasingly recognize the need for robust power management solutions, the FCC 15 is well-positioned to address these challenges, making it a valuable asset for any enterprise seeking to optimize their power infrastructure.