White Rodgers 1F82-261 Troubleshooting, Symptom Possible Cause Corrective Action, Reset Operation

Page 8

TROUBLESHOOTING

Reset Operation

If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation you can reset the thermo-

stat by pressing the reset button (see Fig 1). If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of pur- chase.

Symptom

Possible Cause

Corrective Action

No Heat/No Cool/No Fan

1.

Blown fuse or tripped circuit breaker.

Replace fuse or reset breaker.

(common problems)

2.

Furnace power switch to OFF.

Turn switch to ON.

 

3.

Furnace blower compartment door or

Replace door panel in proper position to engage

 

 

panel loose or not properly installed.

safety interlock or door switch.

No Heat

1.

System Switch not set to Heat.

Set System Switch to Heat and raise setpoint

 

 

 

above room temperature.

 

2.

Loose connection to thermostat or system.

Verify thermostat and system wires are securely

 

 

 

attached.

 

3.

Heating System requires service or

Diagonistic: Set System Switch to Heat and raise

 

 

thermostat requires replacement.

the setpoint above room temperature. Within a five

 

 

 

minutes the thermostat should make a soft click

 

 

 

sound. This sound usually indicates the thermostat

 

 

 

is operating properly. If the thermostat does not

 

 

 

click, try the reset operation listed above. If the

 

 

 

thermostat does not click after being reset contact

 

 

 

your heating and cooling service person or place

 

 

 

of purchase for a replacement. If the thermostat

 

 

 

clicks, contact the furnace manufacturer or a

 

 

 

service person to verify the heating system is

 

 

 

operating correctly.

No Cool

1.

System Switch not set to Cool.

Set System Switch to Cool and lower setpoint

 

 

 

below room temperature.

 

2.

Loose connection to thermostat or system.

Verify thermostat and system wires are securely

 

 

 

attached.

 

3.

Cooling System requires service or thermostat

Same procedure as diagnostic for No Heat

 

 

requires replacement.

condition except set the thermostat to Cool and

 

 

 

lower the setpoint below the room temperature.

 

 

 

There may be up to a five minute delay before

 

 

 

the thermostat clicks in Cooling if the compressor

 

 

 

lock-out option is selected in the configuration

 

 

 

menu (Item 7).

Heat, Cool or Fan Runs Constantly.

1.

Possible short in wiring.

Check each wire connection to verify they are

 

2.

Possible short in thermostat.

not shorted or touching together. No bare wire

 

3.

Possible short in Heat/Cool/Fan system.

should stick out from under terminal screws. Try

 

4.

Fan Switch set to Fan On.

resetting the thermostat as described below.

 

 

 

If the condition persists, the manufacturer of

 

 

 

your system or service person can instruct you

 

 

 

on how to test the Heat/Cool system for correct

 

 

 

operation. If the system operates correctly,

 

 

 

replace the thermostat.

Furnace Cycles Too Fast or Too Slow

1.

The location of the thermostat and/or the size

Item 2 in the Configuration Menu is the adjustment

(narrow or wide temperature swing)

 

of the Heating System may be influencing the

that controls the cycle rate. If an acceptable cycle

 

 

cycle rate.

rate is not achieved using the FA (Fast) or SL

 

 

 

(Slow) adjustment contact a local service person for

 

 

 

additional suggestions.

Cooling Cycles Too Fast or Too Slow

1.

The location of the thermostat and/or the size

The cycle rate for cooling is fixed and can not be

(narrow or wide temperature swing)

 

of the Cooling System may be influencing the

adjusted. Contact a local service person for

 

 

cycle rate.

suggestions.

Thermostat Setting and Thermometer

1.

Thermostat thermometer setting requires

The thermometer can be adjusted +/- 4 degrees as

Disagree

 

adjustment.

listed in item 8 of the Configuration Menu. No other

 

 

 

adjustment is possible.

Clock Loses or Gains Time

1.

Loss of power to thermostat.

The thermostat will maintain its program in memory

 

 

 

even with no power but the clock time will be

 

 

 

incorrect when power is restored. See No

 

 

 

Heat/No Cool/No Fan (common problems) above

 

 

 

for items to check in the system.

Heat or Cool Starts Early

1.

EMR activated

See Configuration Menu (Item 5).

Thermostat Does Not Follow Program

1.

AM or PM set incorrectly in program.

Check current clock and program settings including

 

2.

AM or PM set incorrectly on the clock.

the AM or PM designations for each time period.

 

3.

Voltage spike or static discharge.

If a voltage spike or static discharge occurs use the

 

 

 

Reset Operation listed above.

Blank Display and/or Keypad Not

1.

Voltage Spike or Static Discharge.

If a voltage spike or static discharge occurs use the

Responding

 

 

Reset Operation listed above.

 

 

 

 

Image 8
Contents Precautions SpecificationsDescription Part no -6175DInstallation Thermostat SystemThermostat Base OperationCheck Thermostat Operation Display Configuration MenuConfiguration Menu Planning Your Program Manual OperationProgramming Your Thermostat Entering Your Program Set Current Time and DayEnter Heating Program Enter Cooling ProgramReset Operation TroubleshootingSymptom Possible Cause Corrective Action
Related manuals
Manual 2 pages 25.09 Kb

1F82-261 specifications

The White Rodgers 1F82-261 is a programmable thermostat designed to optimize home heating and cooling systems for energy efficiency and comfort. This device is renowned for its user-friendly interface and versatile programming features, making it a popular choice among homeowners seeking to enhance their climate control while potentially reducing energy bills.

One of the main features of the 1F82-261 is its 7-day programmable schedule. This allows users to set different temperature preferences for each day of the week, accommodating unique lifestyles and preferences. With the ability to program multiple hold times throughout the day, homeowners can ensure their living spaces are comfortable when they're home while saving energy when they're away.

The thermostat is equipped with an easy-to-read digital display, which provides clear visibility of the current temperature settings and the programmed schedule. The simplicity of the buttons and menu navigation ensures that users can quickly adjust their settings or program the thermostat without confusion, making it accessible for all members of the household.

In terms of technology, the 1F82-261 integrates advanced temperature control algorithms that enhance the accuracy of heating and cooling cycles. This precision helps maintain a consistent indoor climate, improving comfort while minimizing energy wastage. Additionally, it features a battery backup system that preserves settings in the event of a power outage, ensuring continuous operation and preventing interruption to the programmed schedules.

Another key characteristic of the White Rodgers 1F82-261 is its compatibility with a variety of HVAC systems, including conventional heating systems, heat pumps, and multi-stage setups. This versatility enables a wide range of homeowners to benefit from its efficiency features, regardless of their existing heating or cooling infrastructure.

Furthermore, the thermostat possesses an intuitive “Hold” function, allowing users to override their programmed settings temporarily. This is especially useful for unexpected changes in schedule or when hosting guests, providing flexibility without the need to reprogram the entire week’s schedule.

Overall, the White Rodgers 1F82-261 combines advanced technology, user-friendly features, and robust compatibility, making it an excellent choice for those looking to improve their home comfort efficiency while keeping energy costs manageable. With its seamless integration into various HVAC systems, intuitive operation, and customizable scheduling, it stands out as a formidable option in the thermostat market.