2
2.2 SETTING UP THE DUAL-RELAY OPTION BOARD
You may enter a setpoint from
LO ALARM
Displayed value is less than Setpoint LO
HI ALARM
Displayed value is more than Setpoint HI
HYSTERESIS
Relay 2 is energized when display value is more than Setpoint HI. Relay 2 is not energized when display value is less than Setpoint LO
Setpoint Example:
Setpoint HI is 500.0 and Setpoint LO is 100.0.
Reading changes from 0 to 600 and back to 0.
Figure 10-2 on the following page illustrates Table 2-1.
Table
|
|
|
|
|
|
|
|
| Alarm Status |
|
|
| Reading | LO (Relay 1) | HI (Relay 2) | HYS |
|
| 0 | On | Off | Off |
|
| 99.9 | Off | Off | Off |
|
| 300 | Off | Off | Off |
|
| 500.0 | Off | Off | Off |
|
| 500.1 | Off | On | On |
|
| 600 | Off | On | On |
|
| 500.1 | Off | Off | On |
|
| 100 - 500 | Off | Off | On |
|
| 99.9 | On | Off | Off |
|
| 0 | On | Off | Off |
|
|
|
|
|
|
|
|
|
|
|
|
|
3