Liebert 3000, 4000, 6000 A, 1500 user manual Framework, Mechanical Specifications of a Cabinet

Page 12

3.0SPECIFICATIONS

3.1Framework

The Helios DC System 4000/48 uses cabinet type frameworks. The same cabinet design is used for the main control and distribution cabinet, the auxiliary distribution cabinets and the rectifier cab- inets. The cabinet is always equipped with a front door and door frame (lockable, equipped with ground straps, and easily removable for installation or maintenance access), a ventilated top cover made of non-flammable plastic, and two ventilated rear cover panels (equipped with ground strap and easily removable for installation and maintenance access). Bussing and equipment (controller, rectifiers, distribution panels, etc.) are added as required, depending on the use of the cabinet. Seismic bracing is also available as options.

When using the Cable Trough, overhead cabling cannot enter from the front or rear of the system. It must be confined to the system foot print and enter at the ends of the lineup.

The cabinets may be either top or bottom cabled as determined by the location of the bussing.

3.1.1 Mechanical Specifications of a Cabinet

The mechanical specifications of an empty cabinet are listed in Table 4.

Table 4

Mechanical specifications of the cabinet (empty)

 

 

 

 

 

 

Framework type

Height

Depth

Width

Weight

 

 

 

 

 

Cabinet

2134 mm

600 mm

600 mm

114 kg

 

 

(84.0 in.)

(23.6 in.)

(23.6 in.)

(251 lb)

 

 

 

 

 

 

Refer to Figure 3 for typical views of cabinets.

3.1.2 Electrical Specifications of the Cabinets

The electrical specifications of equipped cabinets are as follows:

• The main control and distribution cabinet for a 1500 A system has a 2000 A busbar riser and a common equipment panel e/w one 1500 A CHG and DISCH busbar and a 2500 A system shunt.

• The main control and distribution cabinet for a 3000A system has a 3000 A busbar riser and a common equipment panel e/w two 1500 A CHG and DISCH busbars and a 4000 A system shunt.

• The main control and distribution cabinet for a 4000A system has a 3000 A busbar riser and a common equipment panel e/w three 1500 A CHG and DISCH busbars and a 5000 A system shunt.

• A 6000 A system has a 3000 A busbar riser in the main control and distribution cabinet (the CHG and DISCH busbar and the shunt are external).

• The auxiliary distribution cabinet is available with a 2000 or 3000 A busbar riser.

• A 1200 A rectifier cabinet has 1500 A busbar risers for the DC output of the rectifiers.

6 Specifications

Image 12
Contents Helios DC System 4000/48 Page Table of Contents Maintenance OperationReference Documents 7.0 List of Terms Figures Tables Purpose of This Document Applicability of This DocumentDescription Rectifier cabinets Main cabinet Aux dist. cabinetApplications Control and Distribution Cabinets Typical Configurations Control and Distribution cabinet 1200A Rectifier cabinetRectifier cabinets Control and distribution cabinetsAuxiliary distribution cabinets Rectifier Cabinet Capacity Type Qty Cabled top or bottomMechanical Specifications of a Cabinet Electrical Specifications of the CabinetsMechanical specifications of the cabinet empty Framework type Height Depth Width WeightMechanical Specifications of the Conventional Controller Electrical Specifications of the Conventional ControllerMechanical specifications of the Conventional Controller Height Depth Width WeightFuse Panels Mechanical specifications of the fuse panels Mechanical specifications of the fuse panelsDistribution Panels Fuse sizes available for the 20 QFF 0-5 a fuse panelsFront view of the 16 QFF 0-5 a & 12 ABS 5-30 a fuse panels Front view of the 16 QFF 0-5 a & 6 TPN 5-30 a fuse panelsFuse sizes available for the 8 TPN 5-30 a fuse panels Fuse sizes available for the 4 RS100P 70-100 a fuse panelsDC power TPL Fuse sizes available for the 4 TPL 225-600 a fuse panelsDC power TPS Fuse sizes available for the 18 TPS 1-70 a fuse panelElectrical specifications of the fuse panels Electrical specifications of the fuse panelsMechanical specifications of the circuit breaker panels Fuses Busbar Panel number Quantity CapacityFront view of the 24 Plug-In 1-100 a circuit breaker panel Nominal CPC Std Trip CPC Mid Trip CurrentFront view of the 4 70-250 a circuit breaker panel Nominal currentFront view of the 2 400 a circuit breaker panel Electrical specifications of the circuit breaker panels Electrical specifications of the circuit breaker panelsExternally Mounted Battery Return Busbar Mechanical specifications of a single laminationLength Width Thickness Terminating Assemblies Optional Perspective view of the a terminating assembliesMPS300 and MPA100 Power Shelves Shelf model Height Depth Width WeightElectrical Specifications of the Power Shelves Mechanical specifications of the Helios Rectifier 100/48Rectifiers Electrical specifications of the Helios Rectifier 100/48 Electrical specifications of the Helios Rectifier 100/48Front view of the Helios Rectifiers 200I/48 and 200E/48 Standards Total harmonicDistortion THD 600 a and 1200 a Battery Disconnect Unit Optional Mechanical SpecificationsElectrical Specifications Mechanical specifications of the Helios Monitor 3000/48Overall Power System Specifications Mechanical Specifications of Fully Equipped Power CabinetsMechanical specifications of the AC junction box Mechanical specifications of fully equipped power cabinetsEnvironmental Specifications Operating Electromagnetic compliance EMCElectrostatic discharge ESD immunity TransportationVisual indicators Visual indicatorsGeneral Front PanelTransmitted alarms Alarm DescriptionPotentiometers PotentiometersSwitches DIP switchesSwitches DIP switch modulesFuses Test pointsFuse Test pointsRear Panel Terminal blocksTB3 TB4 TB1 TB2 Connectors Rectifiers 600 a and 1200 Battery Disconnect Units Optional Cleaning Helios Monitor 3000/48 Controller and RectifiersCalibration Storage Air filter replacement Fan unit replacementTroubleshooting Fault diagnosisAddition / Replacement Procedures Addition or Replacement of a RectifierAdding a Helios Rectifier 100/48 Adding a Helios Rectifier 200I/48 or 200E/48AC connections in a Helios Rectifier 200E/48 Cover Rect Replacing a Rectifier Replacing a Helios Rectifier 100/48Replacing a Helios Rectifier 200I/48 or 200E/48 Adding or Replacing a Battery String Removal of the old stringReplacement of a Distribution Fuse Block or Circuit Breaker Replacing a Cabinet Alarm LampReplacing a distribution circuit breaker Reference Documents Manual No DescriptionAC or ac DC or dcFt-lb GRD or GrndIn.-lb PsiList of Terms 1500, 3000, 4000 & 6000 a DC Power System Technical Support
Related manuals
Manual 76 pages 7.19 Kb Manual 76 pages 48.63 Kb

1500, 6000 A, 4000, 3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.