TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the PowerSure™ Interactive UPS develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation.

1.The fault indicator will flash every second to indicate the UPS detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

3.One or more additional load/battery level LED segments will be illuminated to provide a diagnostic aid to the operator, as described below:

Load/ Battery

Level Indicators

Utility High/Low Utility Alarm silence/Test On/Off

“D” indicator

Fault indicator (flashes every second)

“B” indicator “A” indicator

A.UPS fault (fan failure, battery overcharge)

NOTE: The internal fan operates intermittently as needed

B.UPS failed battery test

D.UPS shutdown due to output overload time-out

A&B. UPS shutdown due to main input relay failure/output short circuit A&D. UPS shutdown due to over temperature condition

B&D. UPS shutdown due to command from communication ports (remote shutdown or SNMP)

The fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational.

If a problem persists consult your dealer, or contact Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.

19

Image 19
Contents PowerSure Interactive Important Safety Instructions Page Introduction & System Description Automatic Voltage Regulator Major ComponentsMINI-TOWER Installation Rackmount Installation Load/Battery Level Indicators ALL Green Controls and IndicatorsPowersure Interactive MINI-TOWER Models Powersure Interactive RackmountOperation Normal Mode OperationBattery Mode Operation UPS Monitoring Communications Interface PortUPS Intelligent Communications MaintenanceUPS Intellislot Communications MINI-TOWER Battery Replacement VA Model Rackmount Battery Replacement Page Indicator a indicator TroubleshootingProblem Cause Solution Troubleshooting Guide2200 VA Powersure Interactive Typical Battery Discharge CurvesAudible Alarm Conditions Fuse Replacement ProceduresDimensions in mm MINI-TOWER SpecificationsRackmount Specifications Page 700-2200 VA