Liebert 700-2200 VA user manual MINI-TOWER Installation

Page 6

MINI-TOWER INSTALLATION

1.Unpack the UPS carefully noting the packing method. Retain the box and packing material for possible future shipment.

CAUTION: The UPS is heavy (see specifications). Take proper precautions when lifting or moving it.

2.Visually inspect the UPS for freight damage. Report damage to the carrier and your dealer.

3.Locate the UPS indoors where it cannot be accidentally disconnected. Locate it in an area with unrestricted airflow, away from water, flammable liquids, gases, corrosives, or conductive contaminants. Maintain a minimum of four (4) inches (102 mm) clearance around the UPS. Maintain an ambient temperature range of 32° to 104° F (0° to 40° C).

NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery life.

4.Ensuring load equipment is turned off, plug all loads into the UPS output receptacles.

5.Plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National Electric Code (ANSI/NFPA 70) or local codes. Use a 15 amp rated device for the 700, 1000, or 1400 VA units, and a 30 amp device for the 2200 VA unit. The wall receptacle must be grounded.

6.Turn on the UPS, by pressing the On/Off button, then turn on the connected load equipment. The UPS is ready for normal operation.

6

Image 6
Contents PowerSure Interactive Important Safety Instructions Page Introduction & System Description Major Components Automatic Voltage RegulatorMINI-TOWER Installation Rackmount Installation Controls and Indicators Load/Battery Level Indicators ALL GreenPowersure Interactive MINI-TOWER Powersure Interactive Rackmount ModelsNormal Mode Operation OperationBattery Mode Operation Communications Interface Port UPS MonitoringMaintenance UPS Intelligent CommunicationsUPS Intellislot Communications MINI-TOWER Battery Replacement VA Model Rackmount Battery Replacement Page Troubleshooting Indicator a indicatorTroubleshooting Guide Problem Cause SolutionPowersure Interactive Typical Battery Discharge Curves 2200 VAFuse Replacement Procedures Audible Alarm ConditionsMINI-TOWER Specifications Dimensions in mmRackmount Specifications Page 700-2200 VA