Liebert 700-2200 VA user manual Rackmount Installation

Page 7

RACKMOUNT INSTALLATION

1.Unpack the UPS carefully noting the packing method. Retain box and packing material for possible future shipment.

CAUTION: The UPS is heavy (see specifications). Take the proper precautions when lifting or moving the UPS.

2.Visually inspect the UPS for freight damage. Report any damage to the carrier and your dealer.

3.Locate the UPS indoors where it cannot be accidentally disconnected. Locate it in an area with unrestricted airflow, away from water, flammable liquids, gases, corrosives, or conductive contaminants. Maintain a minimum of four (4) inches (102 mm) clearance in front and rear of the UPS. Maintain an ambient temperature range of 32° to 104° F (0° to 40° C).

NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery life.

4.Gently lay UPS on its bottom side so that the front bezel is facing you.

5.The Rackmount UPS must be supported by a shelf or rails. The front bezel will not support the weight of the UPS.

CAUTION: To increase the stability of the rack enclosure, place the UPS in the lowest possible rack position.

6.Refer to the Installation instructions supplied with the Rack Slide or Shelf Kits to complete the installation procedures.

7.After the UPS has been installed in the Rack enclosure, plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National Electric Code (ANSI/NFPA 70) or local codes. Use a 15 amp rated device for the 700, 1000, or 1400 VA units, and a 30 amp device for the 2200 VA unit. The wall receptacle must be grounded.

8.Ensuring load equipment is turned off, plug all loads into the UPS output receptacles.

9.Turn on the UPS, by pressing the On/Off button, then turn on the connected load equipment. The UPS is ready for normal operation.

7

DISCONTINUED

PRODUCT

Image 7
Contents PowerSure Interactive DIS Product Important Safety InstructionsDIS Product Introduction & System Description Automatic Voltage Regulator Major ComponentsMINI-TOWER Installation Rackmount Installation Load/Battery Level Indicators ALL Green Controls and IndicatorsPowersure Interactive MINI-TOWER Models Powersure Interactive RackmountOperation Normal Mode OperationBattery Mode Operation UPS Monitoring Communications Interface PortUPS Intelligent Communications MaintenanceUPS Intellislot Communications MINI-TOWER Battery Replacement VA Model Rackmount Battery Replacement DIS Product Indicator a indicator TroubleshootingProblem Cause Solution Troubleshooting Guide2200 VA Powersure Interactive Typical Battery Discharge CurvesAudible Alarm Conditions Fuse Replacement ProceduresDimensions in mm MINI-TOWER SpecificationsRackmount Specifications DIS Product 700-2200 VA