Liebert 700-2200 VA user manual MINI-TOWER Specifications, Dimensions in mm

Page 23

MINI-TOWER SPECIFICATIONS

Model Number

PS700MT-120

 

PS1000MT-120

PS1400MT-120

 

PS2200MT-120

Model Rating VA/W

700 / 450

 

1000 / 670

1400 / 950

 

2200 / 1600

DIMENSIONS: in (mm)

 

 

 

 

 

 

Unit

5.5 x 14.4 x 7.0

 

6.8 x 17.5 x 8.9

6.8 x 17.5 x 8.9

 

7.6 x 20.1 x 13.2

W x D x H

(140 x 365 x 178)

 

(172 x 447 x 227)

(172 x 447 x 227)

 

(194 x 511 x 336)

 

 

 

 

 

 

Shipping

10.5 x 19.2 x 11.75

 

12.0 x 22.25 x 14

12.0 x 22.25 x 14

 

13.0 x 25.0 x 18.5

W x D x H

(265 x 492 x 300)

 

(307 x 581 x 358)

(307 x 581 x 358)

 

(330 x 635 x 470)

 

 

 

 

 

 

WEIGHT: lbs (kg)

 

 

 

 

 

 

Unit

29.9 (13.6)

 

43.4 (19.7)

49.4 (22.5)

 

81.7 (37.1)

Shipping

33.1 (15.0)

 

46.5 (21.1)

52.5 (23.9)

 

87.0 (39.5)

INPUT AC PARAMETERS

 

 

 

 

 

 

Voltage Range

 

 

120 VAC; -25%, +23%

 

Voltage Raise

Maintains output to 120 VAC; -14%, when input is 120 VAC, -25%

Voltage Lower

Maintains output to 120 VAC; +10%, when input is 120 VAC, +23%

Frequency

 

 

45-55 Hz or 55-65 Hz; auto sensing

 

Input

6 ft. detachable, w/

 

6 ft. attached, w/

6 ft. attached, w/

 

6 ft. attached, w/

Power Cord

NEMA 5-15 P

 

NEMA 5-15 P

NEMA 5-15 P

 

NEMA L5-30 P

 

 

 

 

 

 

OUTPUT AC PARAMETERS

 

 

 

 

 

Output Receptacles

(4) 5-15R

 

(6) 5-15R

(6) 5-15R

 

(6)5-15R (2)5-20R

Voltage

 

 

103 VAC

to 132 VAC

 

 

Max. Current Rating

5.8 A

 

8.3 A

11.67 A

 

18.3 A

Frequency

 

 

50 Hz or 60 Hz

 

Waveform

 

 

Sinewave

 

Utility Mode Overload

 

200% for > 2 cycles; 110% for > 5 minutes

Battery Mode Overload

150% for > 1 cycle; 110% for > 30 seconds

BATTERY PARAMETERS

 

 

 

 

 

 

Type

 

 

Valve-regulated, nonspillable, lead acid

 

Qty. x Voltage x Rating

 

 

 

 

 

 

 

2 x 12V x 7.0 or 7.2 AH

 

3 x 12V x 7.0 or 7.2 AH

4 x 12V x 7.0 or 7.2 AH

 

8 x 6V x 12 AH

 

 

 

 

 

 

Batt. Mfg./ Part Number

CSB: GP1270F2 or Panasonic LC-R127R2CH1

 

Panasonic:

 

 

 

 

 

 

LC-R0612CH1

Transfer Time

 

 

2-6 ms typical

 

 

Back-up Time

 

 

See Typical Battery Discharge Curves

 

Recharge Time

3 Hours

 

3 Hours

5 Hours

 

3 Hours

 

to 95%

capacity, after full

discharge into 100% load

ENVIRONMENTAL

 

 

 

 

 

 

Operating Temperature

 

 

+32° F to + 104° F (0° C to +40° C)

 

Storage Temperature

 

 

+5° F to + 122° F (-15° C to +50° C)

 

Relative Humidity

 

 

0% to 95%, non-condensing

 

Operating Elevation

Up to 10,000 ft. (3000 m) at 35° C without derating

Storage Elevation

 

 

50,000 ft. (15,000 m) maximum

 

Audible Noise

 

 

<45 dBA, at 1 meter

 

AGENCY

 

 

 

 

 

 

Safety

 

 

UL 1778, c-UL Listed

 

RFI/EMI

 

 

FCC Part 15, Subpart B, Class A

 

Immunity

IEC 801-2, Level 4 / IEC 801-4, Level 4 / IEEE 587 Category A

23

DISCONTINUED

PRODUCT

Image 23
Contents PowerSure Interactive DIS Product Important Safety InstructionsDIS Product Introduction & System Description Automatic Voltage Regulator Major ComponentsMINI-TOWER Installation Rackmount Installation Load/Battery Level Indicators ALL Green Controls and IndicatorsPowersure Interactive MINI-TOWER Models Powersure Interactive RackmountOperation Normal Mode OperationBattery Mode Operation UPS Monitoring Communications Interface PortUPS Intellislot Communications MaintenanceUPS Intelligent Communications MINI-TOWER Battery Replacement VA Model Rackmount Battery Replacement DIS Product Indicator a indicator TroubleshootingProblem Cause Solution Troubleshooting Guide2200 VA Powersure Interactive Typical Battery Discharge CurvesAudible Alarm Conditions Fuse Replacement ProceduresDimensions in mm MINI-TOWER SpecificationsRackmount Specifications DIS Product 700-2200 VA