6. MULTIPLE REMOTE CONTROL DISPLAY

You can control several units with a multiple remote control display, by wiring an optional multiple display adapter (PAC-SA88HA-E) with relays and lamps on the market.

How to wire

(1)Connect the multiple display adapter to the connector CN51 on the indoor controller board.

(2)Wire three of the five wires from the multiple display adapter as shown in the figure below.

<Wiring >

 

 

X2

GL

 

 

 

GREEN

 

5

 

 

 

 

X2

 

 

 

 

 

 

 

CN51

 

YELLOW

X1

RL

Power

 

X1

 

 

 

 

supply

1

 

ORANGE

 

 

 

 

 

 

connector(5P)

RED

 

 

 

 

 

 

 

 

 

 

BROWN Electrical insulation is needed.

 

 

 

Optional multiple display

Wiring at the actual place

 

 

adapter

 

 

 

 

The maximum distance between indoor board and relay is 33ft.

<System>

Power3wires

supply3wires 3wires

2wires

No.1 unit

No.2 unit

No.3 unit

 

 

 

 

Remote

Relay box

 

 

controller

(Field supply)

 

 

cable

 

 

Multiple remote contr

o

l

 

 

 

 

 

 

 

 

 

Remote

Remote

Remote

ON-OFF display

 

 

 

(Field supply)

controller

controller

controller

 

 

 

 

 

 

 

 

 

 

(Operation check)

 

 

 

 

 

 

 

 

 

Indoor controller board

CN51

CN51

[Notes on Signs]

X1:Relay (for operation lamp) X2:Relay (for check lamp) RL:Operation Lamp GL:Check Lamp

[Field supplied parts]

Relays:12V DC with rated coil power consumption below 0.9W.

Lamps:Matching to power supply voltage.

<Wiring diagram>

 

 

 

 

 

 

RL-1

X1-1

 

 

Multiple remote

 

 

 

 

Power

GL-1

X2-1

X1-1

1

controller adapter

supply

 

 

 

 

 

 

 

 

X2-1

5

No.1 unit

 

 

 

 

 

 

RL-2

X1-2

 

 

 

 

 

 

 

 

 

GL-2

X2-2

X1-2

1

 

 

 

 

 

 

 

X2-2

 

No.2 unit

 

 

 

5

 

 

 

X1-3

 

 

 

RL-3

 

 

 

 

 

 

 

 

 

GL-3

X2-3

X1-3

1

No.3 unit

 

 

 

 

 

 

 

 

 

 

X2-3

5

connect to

 

 

 

 

 

the connector CN51

Multiple Remote Control Display

 

Relay box

 

 

7. AUTO RESTART FUNCTION

By setting the dip switch SW1-8 to ON, the air conditioner can be started/stopped by power supply ON/OFF. If the air conditioner is OFF before the power failure, it will not start operation by power restore.

•This function is mainly to emergency performance when the power supply stops temporarily. Therefore, since the protec- tion function (for example, clank case heater and prevention from restarting in 3 minutes, etc.) of the device is not operat- ed, this function should not be used mostly.

8. TIMER OPERATION OR THE OPERATION BY AN EXTERNAL SIGNAL

<Wiring>

 

A : an optional timer adapter

A

 

B : a single-throw switch

 

A

B

 

B

Brown

 

Brown

 

Red

Red

 

Orange Remote controller

Orange Remote controller

 

For remote control, connect the optional timer adapter (PAC-SA89TA-E)

OC277-54

Page 54