2-9 Dip switch functions

Each figure shows the initial factory setting.

(1). On remote controller board

1.SW17(Address selector)

12 3 4 5 6 7 8

ON

OFF

SW17-1~6) For address setting

SW17-7) When two remote controllers are used,this switch sets the controller function.

OFF:The remote controller is set as a main controller.

ON:The remote controller is set as a sub controller.

SW17-8) Switch for system back-up.

OFF:Without back-up

ON:With back-up

2.SW18(Function selector)

12 3 4 5 6 7 8

ON OFF

SW18-1) Switch for timer

OFF:Single day ON:timer every day

SW18-2) Switch for filter sign

OFF:filter sign absent

ON:filter sign present

SW18-3) Switch for filter sign time setting.

OFF:100Hr ON:2500Hr

SW18-4~8) Not for use.

(2). On indoor controller board

1. SW1 (Mode selector)

1 2 3 4 5 6 7 8 9 10

ON

OFF

SW1-1) Switch that changes between FAN mode and AUTO mode OFF:AUTO mode for models with heat pump

ON:Fan mode for models without heat pump SW1-2) Switch for drain pump

OFF:The drain pump works in COOL and DRY operation.

ON:The drain pump works in both COOL and DRY and HEAT operation. SW1-3) Switch to change the temperature to start coil frost prevention

OFF:34°F

ON:36°F

SW1-4) Switch for set temperature adjustment in HEAT mode

During HEAT operation,warm air collects near the ceiling.When the indoor unit is installed near the ceiling,the temperature read by room temperature thermistor differs from the actual living-space temperature by about 7 degrees. Therefore,the room temperature read by room temperature thermistor must be lowered by 7 degrees. OFF:7-degree adjustment

ON:NO adjustment

SW1-5) Switch for fan speed during thermostat OFF in HEAT operation

OFF:EXTRA LOW ON:LOW

SW1-6) Switch for fan speed during thermostat OFF in HEAT operation OFF:EXTRA LOW or LOW(set with SW1-5)

ON:LOW or HIGH(set with remote controller)

SW1-7) Switch for detecting abnormalities in the outdoor unit abnormality detection OFF:When an abnormality occurs,it is detected.

ON:Even if an abnormality occurs,it can not be detected. SW1-8) Switch for auto restart function

OFF:This function does not work ON:This function works.

SW1-9, 10) Not for use.