2-2 DRY operation

 

 

SWING

 

TIMER OFF TIMER

CLOCK AUTO AUTO

FAN

 

CHECK SET TEMP.

START STOP

FILTER

SPEED

 

 

AUTO

CHECK MODE

 

 

RETURN

TEST RUN

<DRY operation time chart>

<How to operate>

1Press POWER ON/OFF button.

2Press the MODE button to display “DRY”

3Press the SET TEMP. button to set the desired temperature. NOTE: The set temperature changes 2°F when the SET TEMP.

button is pressed one time. Dry 65 to 87°F

Operation starts by

 

Room temperature

P O W E R b u t t o n

 

becomes equal to

ON.

 

set temperature.

 

 

 

 

 

 

 

 

 

 

 

ON

Thermostat

OFF

 

DRY MODE

 

ON

Indoor fan

OFF

 

ON

Auto vane

OFF

 

Room temperature

 

Operation stops by

rises above set

 

P O W E R b u t t o n

temperature.

 

OFF.

 

 

 

 

 

 

 

 

 

 

DRY MODE

ON

Booster heater OFF

ON Compressor OFF

OFF

Minimum 3 minutes w1

w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.

(1)Compressor control

1 3-minute time delay

To prevent overload, the compressor will not start within 3 minutes after stop.

2The compressor runs when room temperature is higher than set temperature.

The compressor stops when room temperature is equal to or lower than the set temperature.

The compressor maintains the previous state when the room temperature minus the set temperature is 0°F or more, or lower than 2°F.

3The compressor stops in check mode or during protective functions.