11

SYSTEM CONTROL

 

1. VARIETY OF SYSTEM CONTROL FUNCTIONS

1 Group control with

 

 

 

Many units, installed at different locations, can be started

 

 

 

and controlled with a single remote controller. The remote

a single remote

 

 

 

 

 

 

controller can be mounted in a different location using a

controller

 

 

 

 

 

 

non-polar two-wire cable, which can be extended up to

(See page OC277-

 

 

 

Unit

Unit

Unit

500m. A maximum of 50 units can be controlled with a

51.)

 

 

Remote

 

 

single remote controller. All units operate in the same

 

 

 

 

 

 

controller

 

 

mode.

2 Control using two

 

 

 

Two remote controllers can be used to control either one

 

 

 

unit or a group of units. Units can then be controlled from

remote controllers

 

 

 

 

 

 

a distance or at close range. Units operate according to

(See page OC277-

 

 

 

 

 

 

the latest command from either remote controller.

52.)

 

Unit

Unit

Unit

 

 

 

 

Remote

 

 

 

 

 

controller

 

 

 

3 Both remote

Optional

 

 

All units can be turned on or off simultaneously using a

adapter

 

 

remote ON-OFF switch. Also, each unit can be controlled

ON/OFF and indi-

 

Relay box

 

 

individually by each remote controller. Dunning remote

vidual controls

 

 

 

(See page OC277-

 

 

 

ON-OFF control, a message of “CENTRALLY CON-

52.)

 

 

 

Unit

TROLLED” is displayed on the LCD of the remote con-

w Timer adapter

 

 

troller.

 

 

 

(PAC-SA89TA-E)

Remote

Remote

 

This is available for both one unit control and several units

is needed.

ON/OFF

controller

control.

 

 

switch

 

 

 

4 Individual control

 

 

 

By grouping the remote controllers in one place, several

 

 

 

units installed at different locations can be controlled indi-

by grouping

 

 

 

 

 

 

vidually, and operation conditions of all units are visible

remote controllers

 

 

 

 

 

 

without a special control board. The control method is the

(See page OC277-

Unit

Unit

Unit

53.)

 

 

 

same as that of the single unit with a single remote con-

 

 

 

troller.

 

Remote

 

 

 

 

 

 

 

controller

 

 

 

5 Multiple remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Several units can be controlled with a remote control dis-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

play board. Operation conditions of all the units are visi-

control display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ble with the remote control display board.

(See page OC277-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Individual control by each remote controller is also possi-

 

 

 

 

 

Unit

 

 

Unit

 

 

Unit

w Multiple display

 

 

 

 

 

 

 

 

 

ble.

adapter

Remote control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

 

 

 

 

(PAC-SA88HA-E)

 

 

 

 

 

 

is needed.

display board

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 Auto restart func-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A unit can be started or stopped with the circuit breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on or off.

tion

Circuit breaker

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller is also available.

(See page OC277-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With this function, when the power is restored after power

54.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

failure, the unit will restart automatically. (However, when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the remote controller POWER ON/OFF button is OFF, the

 

 

 

 

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit will not start.)

OC277-50