Liebert GXT96VLRT2UL user manual Important Safety Instructions

Page 2

IMPORTANT SAFETY INSTRUCTIONS

WARNING: Do not attempt to service this product yourself. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical outlet. Refer all servicing to qualified service personnel.

1.SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS THAT SHOULD BE FOLLOWED DURING INSTALLATION AND MAINTENANCE OF THE BATTERY CABINET AND UNINTERRUPTIBLE POWER SYSTEM (UPS).

2.This product is not intended for use with life support and other U.S. FDA designated “critical” devices. See Limited Warranty.

3.CAUTION: A BATTERY PRESENTS A RISK OF ELECTRICAL SHOCK OR BURN FROM HIGH SHORT CIRCUIT CURRENT. OBSERVE PROPER PRECAUTIONS.

4.WHEN REPLACING THE BATTERIES, USE THE SAME NUMBER AND TYPE OF BATTERIES. PROPER DISPOSAL OF BATTERIES IS REQUIRED. REFER TO YOUR LOCAL CODES FOR DISPOSAL REQUIREMENTS.

5.Read all safety and operating instructions before operating the UPS and battery cabinet. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions.

6.Turn the UPS and battery cabinet off and unplug them before cleaning. Use only a soft cloth, never liquid or aerosol cleaners.

7.The UPS is designed for data processing equipment. Do not plug appliances, such as hair dryers, heaters, vacuum cleaners, or electric drills, into the UPS output receptacles. The UPStation GXT™ LRT has a nominal voltage rating of 96VDC. The UPStation GXT™ LRT is designed to operate only with the Liebert UPStation GXT 1800/2000 and 2700/3000 VA rack tower (RT) UPS units with a sequential serial number 9915003001AF1T1 or greater. The LRT cabinets are capable of being paralleled in order to achieve longer run times (up to 8+ hours).

8.WARNING: Do not modify input cable. Consult your dealer if connector does not match the utility receptacle. The UPS and Battery Cabinet must be grounded at all times while in use. Turn the UPS and Battery Cabinet off before unplugging them, or the safety ground will be removed. Operate Battery Cabinet only from a properly grounded 120 or 230 VAC outlet (2 wire plus ground).

9.The Battery Cabinet is equipped with a grounded NEMA 5-15, or a grounded Schuko- type input power plug (depending upon input voltage). Do not defeat the safety purpose of this plug. If unable to fully insert the plug into the wall outlet, contact a qualified electrician for assistance.

10.Route power supply cords so they are not walked on or pinched.

11.Never block or insert any object into the ventilation holes or other openings. Maintain a clearance of four (4) inches in front and rear of the Battery Cabinet for proper airflow and cooling.

12.Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Refer all servicing to qualified service personnel.

13.CAUTION: Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic.

14.CAUTION: This equipment has been tested and complies with limits for a Class A digital device, pursuant to Subpart B of Part 15 of FCC rules; and the CE EMC directive. These limits provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference that the user must correct at their own expense.

15.This equipment can be operated by individuals without previous training.

2

DISCONTINUED

PRODUCT

Image 2
Contents UPStation GXT 1800-3000 VAImportant Safety Instructions Unpacking the LRT General Installation GXT / LRT Installation Controls and Indicators Lrttm Battery Cabinet Specifications GXT96VLRT2ULLimited Warranty UPStation GXT Lrttm Battery Cabinet 1800-3000 VA

GXT96VLRT2UL specifications

The Liebert GXT96VLRT2UL is a high-performance uninterruptible power supply (UPS) designed to provide reliable backup power and enhanced protection for critical electronic equipment. With its advanced features and robust design, it caters to the needs of various applications, including data centers, telecom systems, and industrial environments.

One of the standout features of the GXT96VLRT2UL is its double-conversion topology. This technology ensures that the equipment connected to the UPS receives a constant flow of clean and reliable power by converting incoming AC to DC and then back to AC again. This process effectively eliminates voltage fluctuations, surges, and electrical noise, ensuring that sensitive equipment operates optimally without interruption.

The GXT96VLRT2UL boasts a high input power factor, supporting energy efficiency and reducing the overall electrical demand. This is particularly crucial for organizations looking to minimize their power consumption and operational costs. Additionally, it has an output power rating of 10 kVA, making it suitable for handling substantial loads efficiently.

Another important characteristic is its flexible design. The Liebert GXT96VLRT2UL can be configured in both tower and rackmount modes, allowing it to adapt to different server room designs and space constraints. This versatility enables users to maximize available space while ensuring effective power management.

Furthermore, this UPS features a comprehensive digital display that provides real-time monitoring of power conditions and battery status. This user-friendly interface allows operators to easily access vital information regarding the UPS’s performance, making it easier to manage and maintain the system.

The Liebert GXT96VLRT2UL is equipped with Intelligent Battery Management technology, which extends battery life and optimizes recharge times. This feature helps reduce maintenance costs and ensures that the UPS is always ready to respond to power disruptions.

Additional enhancements include customizable alarms and notifications that keep users informed of any potential issues. Remote monitoring capabilities also allow for proactive management, increasing the reliability of the power protection strategy.

With its combination of advanced features, robust performance, and flexibility, the Liebert GXT96VLRT2UL stands out as a reliable choice for businesses seeking to protect their critical infrastructure from power disturbances. Its ability to ensure continuous operation during outages makes it an essential component in maintaining business continuity.