Liebert GXT96VLRT2UL user manual General Installation

Page 4

GENERAL INSTALLATION

LRT CABINET INSTALLATIONS

1.CAUTION: The LRT cabinet is heavy (see specifications). Take proper precautions when lifting or moving it.

2.Remove the retaining straps and protective cardboard covering from the shipping package.

3.Remove the 14mm (9/16”) hex bolts from the side of the shipping crate. Retain one hex bolt and the side of the shipping crate.

4.Remove the four wood planks from each corner of the shipping crate. Remove the top of the shipping crate from the LRT cabinet.

5.Place the side of the shipping crate at the bottom of the crate and insert one hex bolt in the crate bottom. The LRT cabinet can now be rolled off of the shipping crate.

6.Visually inspect the LRT cabinet for freight damage. Report damage to the carrier and your dealer.

7.Locate the LRT cabinet indoors in a controlled environment, where it cannot be accidentally disconnected. Locate it in an area with unrestricted air flow, away from water, flammable liquids, gases, corrosives, or conductive contaminants. Maintain a minimum of 4 inches (100 mm) clearance in front and rear of the LRT cabinet. Battery cabinets are designed to be placed on either side of, or beneath the UPS. Maintain an ambient temperature range of 32° to 104° F (0° to 40° C).

NOTE: LRT cabinet operation in temperatures above 77° F (25° C) reduces battery life.

8.Plug the LRT cabinet into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National and Local Codes. Use a 15 amp rated device for 120VAC applications, or a 10 amp rated device for 230VAC applications. The wall receptacle must be grounded, and should be wired so as to experience outages simultaneously with the connected UPStation GXT™ UPS.

CAUTION: Do not use the UPS output receptacles as the LRT input power source.

9.Connect the supplied cable to the battery cabinet then to the UPS. Turn on the charger by pressing the On switch located on the rear panel. Turn on the breaker on the rear of the battery cabinet. The LRT cabinet is ready for normal operation. Up to three optional LRT cabinets may be connected to the UPS to provide additional run time.

4

DISCONTINUED

PRODUCT

Image 4
Contents UPStation GXT 1800-3000 VAImportant Safety Instructions Unpacking the LRT General Installation GXT / LRT Installation Controls and Indicators Lrttm Battery Cabinet Specifications GXT96VLRT2ULLimited Warranty UPStation GXT Lrttm Battery Cabinet 1800-3000 VA

GXT96VLRT2UL specifications

The Liebert GXT96VLRT2UL is a high-performance uninterruptible power supply (UPS) designed to provide reliable backup power and enhanced protection for critical electronic equipment. With its advanced features and robust design, it caters to the needs of various applications, including data centers, telecom systems, and industrial environments.

One of the standout features of the GXT96VLRT2UL is its double-conversion topology. This technology ensures that the equipment connected to the UPS receives a constant flow of clean and reliable power by converting incoming AC to DC and then back to AC again. This process effectively eliminates voltage fluctuations, surges, and electrical noise, ensuring that sensitive equipment operates optimally without interruption.

The GXT96VLRT2UL boasts a high input power factor, supporting energy efficiency and reducing the overall electrical demand. This is particularly crucial for organizations looking to minimize their power consumption and operational costs. Additionally, it has an output power rating of 10 kVA, making it suitable for handling substantial loads efficiently.

Another important characteristic is its flexible design. The Liebert GXT96VLRT2UL can be configured in both tower and rackmount modes, allowing it to adapt to different server room designs and space constraints. This versatility enables users to maximize available space while ensuring effective power management.

Furthermore, this UPS features a comprehensive digital display that provides real-time monitoring of power conditions and battery status. This user-friendly interface allows operators to easily access vital information regarding the UPS’s performance, making it easier to manage and maintain the system.

The Liebert GXT96VLRT2UL is equipped with Intelligent Battery Management technology, which extends battery life and optimizes recharge times. This feature helps reduce maintenance costs and ensures that the UPS is always ready to respond to power disruptions.

Additional enhancements include customizable alarms and notifications that keep users informed of any potential issues. Remote monitoring capabilities also allow for proactive management, increasing the reliability of the power protection strategy.

With its combination of advanced features, robust performance, and flexibility, the Liebert GXT96VLRT2UL stands out as a reliable choice for businesses seeking to protect their critical infrastructure from power disturbances. Its ability to ensure continuous operation during outages makes it an essential component in maintaining business continuity.