Liebert 2U user manual Introduction and System Description

Page 7

INTRODUCTION AND SYSTEM DESCRIPTION

Congratulations on your choice of the Liebert 2U POD. The Liebert 2U POD provides main- tenance bypass capability as well as power output distribution. The Liebert 2U POD can be used on UPSs in the rack mount or tower configuration.

The Liebert 2U POD provides an isolated path of power for your UPS system for preventive maintenance or service.

System Description

The 2U POD has two modes of operation: UPS (UPS available) and MAINS (maintenance bypass).

In UPS mode, the power is routed through the UPS system delivering conditioned power to the load, as shown in Figure 1.

Figure 1 UPS mode of operation

Mains

POD

Connected loads

UPS

In MAINS mode, the power is routed around (bypassing) the UPS system (see Figure 2). Mains power is supplied directly to the load through the 2U POD.

!CAUTION

Battery back-up and conditioned power are NOT available during the MAINS mode of operation.

Figure 2 MAINS/maintenance bypass mode

Mains

POD

Connected loads

UPS

• The UPS may be turned off and removed without affecting the load. See Figure 3.

Figure 3 2U POD connections

UPS INPUT

Rotary switch

MAINS INPUT

Connect to load socket on

and power

Connect to mains wall socket. Use

rear of UPS. Cable supplied.

indicator lamps.

original UPS mains input cord.

 

 

UPS

MAINTENANCE BYPASS

 

 

AVAILABLE

AVAILABLE

10A

A

10A

CIRCUIT BREAKER

16A 250V-/T

 

UPS

MAINS

 

 

CAUTION

CONNECT UPS LINE CORD HERE

 

 

 

 

 

IF MAINS LAMP IS ILLUMINATED

 

 

 

MAINTENANCE BYPASS POSITION

 

 

 

MAY BE SELECTED.

 

UPS

 

SWITCH TO UPS POSITION ONLY

MAINS

 

WHEN UPS LAMP IS ILLUMINATED.

 

 

A+B MAX. 16A

 

B

10A

 

 

 

 

 

 

 

 

Connect UPS

 

 

 

 

input cord here.

 

 

Connect loads.

Cable supplied.

Connect loads.

3

Image 7
Contents 2U POD Page Table of Contents Page Important Safety Instructions Mains UPS Glossary of SymbolsSystem Description Introduction and System DescriptionAttaching POD securing brackets to rear of UPS Installation on GXT 2U UPSAttaching POD to securing brackets 10A Rack Mount InstallationMains Indicator Lamp Indicator LampsOperation Transfer to Maintenance BypassSpecifications Illuminated TroubleshootingPage Company Behind the Products