LaCie 12big Rack Storage Server manual Introduction, Preparation

Page 3

1. INTRODUCTION

1.1. Safe Handling

ƒƒ An enclosure can weigh up to 36kg (79.2lb). Do not try to lift it by yourself.

ƒƒ Do not lift the enclosure by the handles on the Battery Modules. They are not designed to take the weight.

1.2. Safety

All plug-in modules and blank plates are part of the fire enclosure and must only be removed when a replacement can be immediately added. The system must not be run without all units in place. In order to com- ply with applicable safety, emission and thermal requirements no covers should be removed.

Permanently unplug the unit if you think that it has become damaged in any way and before you move it.

ƒƒ The unit must only be operated from a power supply input voltage range of 100-240 VAC, 50-60 Hz.

ƒƒ The plug on the power supply cord is used as the main disconnect device. Ensure that the socket outlets are located near the equip- ment and are easily accessible.

ƒƒ The power connection must always be disconnected prior to re- moval of a PSU module from the enclosure.

ƒƒ A safe electrical earth connection must be provided to the power cord. Check the grounding of the enclosure before applying power.

ƒƒ Provide a suitable power source with electrical overload protection to meet the requirements laid down in the technical specification.

ƒƒ This equipment is intended to operate with two working PSUs in- stalled in the Power Supply Module. Before removal/replacement of a PSU disconnect all power for isolation.

ƒƒ A faulty PSU must be replaced with a fully operational one within 24 hours.

CAUTION: If this equipment is used in a manner not specified by LaCie, the protection provided by the equipment may be impaired.

IMPORTANT INFO: The enclosure top cover must be secured, when the enclosure is in normal use, by rotating the lock 90° to the ‘locked’ posi- tion. This is to prevent users/operators from accessing the service areas.

CAUTION: The RJ45 sockets on the motherboard/PCI cards are for Eth- ernet connection only and must not be connected to a telecommunica- tions network.

IMPORTANT INFO: Do not remove covers from the PSU. Danger of electric shock inside. Return the PSU to LaCie for repair.

IMPORTANT INFO: Bifurcated power cords must NOT be used with the 12big Rack Storage Server.

1.3. ESD Precautions

It is recommended that you fit and check a suitable anti-static wrist or ankle strap and observe all conventional ESD precautions when handling plug-in modules and components. Avoid contact with backplane compo- nents and module connectors, etc.

1.4. Rack System Precautions

The following safety requirements must be considered when the unit is mounted in a rack.

ƒƒ The rack design should incorporate stabilizing features suitable to prevent the rack from tipping or being pushed over during installa- tion or in normal use.

ƒƒ When loading a rack with the units, fill the rack from the bottom up and empty from the top down.

ƒƒ The rack design should take into consider-ation the maximum op- erating ambient temperature for the unit, which is 35°C.

ƒƒ The system must be operated with low pressure rear exhaust instal- lation (back pressure created by rack doors and obstacles not to exceed 5 pascals (0.5mm water gauge)).

ƒƒ The rack should have a safe electrical distribution system. It must provide over-current protection for the unit and must not be over- loaded by the total number of units installed in the rack. Consid- eration of the electrical power consumption rating shown on the unit’s nameplate should be used when addressing these concerns.

ƒƒ The electrical distribution system must provide a reliable earth for each unit in the rack.

ƒƒ Each power supply in each unit has an earth leakage current of 0.75mA. The design of the electrical distribution system must take into consideration the total earth leakage current from all the power supplies in all the units. The rack will require labelling with “HIGH LEAKAGE CURRENT. Earth connection essential before connecting supply”.

ƒƒ The rack, when configured with the units, must meet the safety re- quirements of UL 60950-1 and IEC 60950-1.

2. PREPARATION

2.1. Before You Begin

Before you begin, make sure the site where you intend to set up and use your enclosure has the following:

ƒƒ Standard power from an independent source or a rack power dis- tribution unit with a UPS.

ƒƒ Power Cord

ƒƒ Rack kit (if installing within a rack)

Refer to LaCie for a list of qualified accessories for use with the enclosure.

The Accessory Box contains the power cords and other ordered acces- sories.

LaCie Quick Install Guide

3

Image 3
Contents 12big Rack Storage Server Table of Contents Preparation IntroductionInstallation UnpackingMounting the System into a Rack Fitting Modules Removing PSUsFitting PSUs Battery Safety Replacing a FanFitting Drives LED Operator PanelMigrating your RAID configuration Managing Your RAIDStart up and log Create a RAID-Protected Disk Array Select Drives for RAID ConfigurationMount the Array Share the volumeContact Us