Eaton Electrical Wiring SPD to Electrical System, XT-40 & IT-RSS Mounting Dimensions

Page 9

XT-40 & IT-RSS Installation

IM01005012E

 

 

Figure 2-2. XT-40 & IT-RSS Mounting Dimensions

 

 

5.58

 

 

 

 

 

(141.7)

 

 

 

 

 

4.73

 

 

 

 

 

(120.1)

 

0.75 (19.0) Internally

 

 

3.23

 

 

 

Threaded Conduit Fitting

 

 

(82.0)

 

 

 

 

 

 

4.17

 

 

 

 

 

(105.9)

 

 

 

 

 

4.80

 

 

 

 

 

(121.9)

 

 

 

2.40

 

 

 

 

 

 

 

 

 

 

(61.0)

 

 

Mounting Holes

1.77

 

 

 

Under Lid (4)

(45.0)

1.38

 

 

 

 

3.15

(35.1)

Note: Remove cover to

2.87

 

2.48

(80.0)

 

 

 

 

gain access to the

(73.0)

 

(63.0)

 

 

mounting hole shafts.

0.79

 

3.15

 

 

 

(20.1)

 

(80.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.25

 

 

 

 

 

 

 

Mounting

 

 

 

 

 

 

 

 

 

Weight: 3 lb

 

 

 

(6.4)

 

 

 

 

 

 

 

Hole Shafts

 

 

 

 

 

 

 

 

 

 

Dimensions: Inches (mm)

2.7Wiring SPD to Electrical System

Important! When connecting the wires from the SPD to the electrical system, cut the wires as necessary to keep them as short as possible. In addition, to maximize the SPD’s performance, also twist and bind the wires together to reduce the impedance of the wire.

1.Locate your electrical system’s applicable wiring diagram in Section 2.2 or 2.3. Reference this wiring diagram as necessary in Steps 2, 3, and 4.

2.Connect the Ground wire (green) from the SPD to the system’s Ground bus bar.

Important! If the system utilizes an isolated ground, then its ground wire must be connected to the system’s isolated Ground bus.

3.For the XT-40, connect the Neutral wire (white) from the SPD to the system’s Neutral bus bar (not required for 3-Phase Delta systems – NN201, NN400, and NN501).

4.Connect each Phase wire from the SPD through one of the circuit interrupt devices installed in Section 2.4 to the system’s corresponding Phase voltage connection.

Tip: To ensure that the front panel phase voltage LEDs glow evenly, be sure that the phase wires are attached to their associated phase (A to A, B to B, and C to C). The wires or terminals of the SPD are marked with the intended phase for the electrical system (A, B, or C). Use a phase rotation meter to identify the electrical system’s phase sequence prior to wiring the SPD — DO NOT trust existing markings.

Rev. 1 – 2/2007

Page 7

Image 9
Contents Innovative Technology Tvss Products XT-40 & IT-RSS IM01005012ERegister Your Warranty On-Line at IT-RSS System Wiring and Maximum Voltages ScopeXT-40 Catalog Numbering System Safety Precautions Before Installation InstallationSingle Phase 1P101, 1P201 Split Phase 1S101 XT-40 Wiring DiagramsInstalling Circuit Interrupt Devices IT-RSS Wiring DiagramMounting the SPD Conduit InstallationXT-40 & IT-RSS Mounting Dimensions Wiring SPD to Electrical SystemPower Up and System Checkout XT-40 & IT-RSS Installation IM01005012E USA