UPS Rating (0.9 power factor)

kVA

225

275

550

 

kW

202

250

500

 

General Characteristics

 

 

 

 

Efficiency

Up to 95%

 

 

Parallel Capability

Up to 3 modules, 550 kVA maximum

Audible Noise

< 65dBA @ 1 meter

 

Altitude (max)

2000m at 40ºC (104ºF)

 

N+1 Redundancy Capable

Yes

 

 

 

Field Upgradeable

Yes, 275 kVA increments

 

System Bypass Module

Included

 

 

Input Characteristics

 

 

 

 

Voltage

480V standard; 208V and 600V with isolation

 

transformer option

 

Voltage Range

+10% / -15%

 

Frequency Range

55-65 Hz

 

 

Power Factor

0.99 (minimum)

 

Input Current Distortion

<3% (no input filter required)

Soft Start Capability

Yes

 

 

 

Internal Backfeed

Yes

 

 

 

Protection

 

 

 

 

Output Characteristics

 

 

 

 

Voltage

480V standard; 208V and 600V with isolation

 

transformer option

 

Regulation

±1%

 

 

 

Inverter

PWM with IGBT switching

 

Voltage THD

<2% (100% linear load); <5% (non-linear load)

Load Power Factor Range

Up to a .9 power factor leading without de-rating

Battery

 

 

 

 

Battery Types

VRLA, AGM, Gel, Wet

 

Battery Voltage

480V

 

 

 

Temperature Compensation

Optional

 

 

Charging Method

Advanced Battery Management technology

Dimensions & Weights

 

 

 

 

225 kVA, 275 kVA

52.4”w x 34.3”d x 73.7”h

1786 lb.

225 kVA redundant,

73.7”w x 34.3”d x 73.7”h

2875 lb.

275 kVA redundant

 

 

 

 

550 kVA

73.7”w x 34.3”d x 73.7”h

2977 lb.

550 kVA redundant

95.0”w x 34.3”d x 73.7”h

4153 lb.

Field upgrade module,

21.3”w x 34.3”d x 73.7”h

1176 lb

225 or 275 kVA

 

 

 

 

Powerware® 9395-825 - Available Fall 2008

Uninterruptible Power System (UPS)

225 to 825 KVA

User Benefits

Control Panel (LCD)

8 lines x 40 characters

Battery Startup

Standard

 

 

Frequency Conversion

Standard

Remote Display Panel

Optional

Multi-language

Standard

 

 

Building Alarm Inputs

6 (galvanic isolated)

Serviceability

 

Back/Side Against Wall

Standard

Installation

 

 

 

Options

External Maintenance Bypass

Powerware PDU, RPP, and STS

Isolation Transformer

Output Transformer

Maintenance Bypass Module

Certifications

Safety

UL1778, cUL

 

 

EMC

FCC Class, A

Surge

ANSI C62, 41 Cat, A&B

eNotify Remote Monitoring

24x7 remote monitoring of 43 UPS and battery alarms, daily heartbeat check and monthly report ConnectUPS Web/SNMP/xHub card

Communications

Software Compatibility - PowerVision®, LanSafe®, FORESEER® , Power Xpert Communication Cards - Standard system includes one ConnectUPS Web/SNMP card with an Environmental Monitoring Probe. Four communication bays standard.

The following connectivity options can be installed at any time:

-ConnectUPS Web/SNMP/xHub

-Modus Card

-Relay Interface Card (Use for AS400s)

-Industrial Relay Card (5A@120V)

-Hot Sync CAN Bridge Card provides CAN communications, isolated RS-485 port

-Environmental Monitoring Probe (EMP)3

Remote Inputs/Outputs - Six building alarms inputs and one summary alarm contact (5A@120V) standard

Remote Panel - Eight backlit status indicator lamps plus an audible horn3

2. Due to continuing improvements, specifications are subject to change without notice.

3. Requires the ConnectUPS Web/SNMP/xHub card.

Europe/Middle East/Africa

Asia Pacific

Denmark: 45.3686.7910

Australia/NZ: 61.2.9693.9366

Finland: 358.94.52.661

China: 86.21.6361.5599

France: 33.1.6012.7400

HK/Korea/Taiwan: 852.2745.6682

Germany: 49.7841.666.0

India: 91.11.2649.9414 to 18

Italy: 39.02.66.04.05.40

Singapore/SEA: 65.6825.1668

Norway: 47.23.03.65.50

Powerware, PowerVision, FORESEER, Power

Sweden: 46.8.598.940.00

United Kingdom: 44.1753.608.700

Xpert, LanSafe, and ABM are trademarks of

 

Eaton Electrical Inc.

 

© 2007 Eaton Corporation

 

All Rights Reserved

 

Printed in USA

 

9395FXA

 

March 2007

For additional information, please call 1-800-392-3299 or email info@naat.com www.naat.com

Image 4
Contents Unmatched power performance and efficiency Best total reliabilityUninterruptible Power System UPS Service design maximizes uptimeService and support enhance performance Advanced software allows you to see the entire pictureUPS Rating 0.9 power factor Input CharacteristicsBattery Serviceability