CyberPower Systems K01-0000063-00 user manual Important Safety Warnings, Basic Operation

Page 1
HARDWARE INSTALLATION GUIDE

CP685AVRLCD-G / CP825AVRLCD-G

User’s Manual

K01-0000063-00

IMPORTANT SAFETY WARNINGS

(SAVE THESE INSTRUCTIONS)

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.

CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).

CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. There are no user serviceable parts inside except for battery.

CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.

CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the unit.

CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer component.

CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code, ANSI/NFPA 70.

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical applications. DO NOT use in any circumstance that would affect operation, safety of any life support equipment, any medical applications or patient care.

DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation from the aquarium can cause the unit to short out.

INSTALLING YOUR UPS SYSTEM

UNPACKING

Inspect the UPS upon receipt. The box should contain the following:

(1)UPS unit; (1) User’s manual; (1) PowerPanel® Personal Edition software CD; (1) USB device cable; (1) Telephone cable; (1) Warranty registration card; (1) Coaxial Cable

WHAT IS AVR

The CP685AVRLCD-G / CP825AVRLCD-G provide complete power protection from utility power that is not always consistent. The CP685AVRLCD-G / CP825AVRLCD-G feature 890 Joules / 1030 Joules of surge protection, and provide long lasting battery backup during power outages with maintenance free batteries. The CP685AVRLCD-G / CP825AVRLCD-G ensure consistent power to your computer system and include software that will automatically save your open files and shutdown your computer system during a utility power loss.

AUTOMATIC VOLTAGE REGULATOR

The CP685AVRLCD-G / CP825AVRLCD-G stabilize utility power voltage levels that can be inconsistent. The incoming utility power may be damaging to important data files and hardware, but with Automatic Voltage Regulation, the computer will not experience damaging voltage levels. An Automatic Voltage Regulator automatically increases low or decreases high voltage to a consistent, computer safe 110v/120v. The unit’s powerful battery will provide power only if the incoming voltage drops below 90v or increases above 140v.

SYSTEM FUNCTIONAL BLOCK DIAGRAM

Input

EMI

 

Surge

 

 

AVR

 

 

Output

Filter

 

Suppressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charger

 

 

 

Inverter

 

 

 

 

 

AC/DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Mode

Battery Mode

Battery

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

1.Ensure that the equipment plugged into the outlet does not exceed the UPS unit’s rated capacity (685VA/390W for CP685AVRLCD-G, 825VA/450W for CP825AVRLCD-G). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.

2.There are many factors that can affect the amount of power that your computer system will require. It is suggested that the load you will be placing on the outlet not exceed 80% of the unit’s capacity.

1.Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8 hours is recommended to ensure that the battery’s maximum charge capacity is achieved. A loss of charge may occur during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet.

2.With the UPS unit off and unplugged, connect your computer, monitor, and any other peripherals requiring battery backup into the battery power supplied outlets. Plug your

other peripheral equipment (printer, scanner, speakers) into the full-time surge protection outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large electrical device into battery and surge protected outlets. The power demands of these devices will overload and possibly damage the unit.

3.To protect a network connection from surges, connect a network cable into the IN jack of the UPS. Then connect a network cable from the OUT jack on the UPS to the network device.

4.Plug the UPS into a 2 pole, 3 wire grounding receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips.

5.Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will “beep”.

6.If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on.

7.To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.

8.To store your UPS for an extended period, cover it and store with the battery fully charged. While in storage recharge the battery every three months to ensure battery life.

BASIC OPERATION

DESCRIPTION

Battery and Surge Protected Outlets

The unit has four battery powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your equipment during a power failure.( DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large electrical device into battery and surge protected outlets. The power demands of these devices will overload and possibly damage the unit.)

Full-Time Surge Protection Outlets

The unit has four surge suppression outlets which are always on

Power Switch

Press the power button to turn the UPS ON or OFF.

Power On Indicator

This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes.

Electrical Wiring Fault Indicator

This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If this is illuminated, it is recommended to disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The unit will not provide surge protection without being plugged into a grounded and properly wired wall outlet.

Communication Protection Ports

Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45).

Circuit Breaker

Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.

USB Port

Allows for connection and communication between the USB port on the computer and the UPS unit. The UPS communicates its status to

the PowerPanel® Personal Edition software. This interface is also compatible with the Power Management provided by Windows® Vista.

Note: To install PowerPanel® Personal Edition Software the computer will need MicrosoftR Internet Explore 6.0 or higher installed.

Outlets Designed for AC Adapters

The unit has four outlets spaced to allow AC power transfomers to be plugged into the UPS without blocking adjacent outlets.

Coax/Cable/DSS Surge Protection

The Coax/Cable/DSS surge protection ports will protect any cable modem, CATV converter, or DSS receiver.

LCD Module Display

 

 

Crystal Blue intelligent LCD panel shows all the UPS information using icons and messages. For

 

 

more information please check the “Definitions for Illumination LCD Indicators” section below.

The LCD display indicates a variety

LCD Panel Toggle Switch

of UPS operational conditions. All

 

The switch can be used to select the LCD panel displayed information including Input Voltage,

descriptions apply when the UPS is

 

Output Voltage and Estimated Run Time. The toggle frequency is set to one time per second.

plugged into an AC outlet and turned

 

Holding the switch for more than two seconds while running on battery will silence the buzzer.

on or when the UPS is on battery.

DEFINITIONS FOR ILLUMINATED INDICATORS

DEFINITIONS FOR ILLUMINATED LED INDICATORS

 

 

 

CONDITION

Power ON

Wiring Fault

Alarm

 

 

 

 

 

On

Off

Off

Normal

On

On/Off

Two Beeps

Utility Failure- The UPS is providing power to battery power-supplied outlets from

the battery.

 

 

 

On

On/Off

Rapid Beeps

Utility Failure- The UPS is providing battery power. Rapid beeps indicate the unit

will run out of power shortly.

 

 

 

 

 

 

System Overload- Occurs when connected equipment exceeds the rating of unit.

Off

Off

Long Beep

Turn the UPS off, unplug at least one piece of equipment, wait 10 seconds, reset the

 

 

 

circuit breaker and turn the unit on.

 

 

 

Battery Overload- Occurs when connected equipment exceeds the rating of battery

Off

On/Off

Long Beep

outlets of the unit. Turn the UPS off, unplug at least one piece of equipment from

 

 

 

battery outlets, wait 10 seconds, reset the circuit breaker and turn the unit on.

 

 

 

 

 

 

 

Electrical Wiring Fault- This indicates a wiring problem with the AC outlet such

On/Off

On

None

as bad ground, missing ground, or reversed wiring. User is advised to disconnect

all electrical equipment from the outlet and have an electrician check the outlet to

 

 

 

 

 

 

verify proper wiring.

DEFINITIONS FOR ILLUMINATED LCD INDICATORS

Line mode

Select SW

UPS Status Display

 

Capacity Display

 

Digital Value Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

Load

Battery

Input

Output

Run

%

%

 

 

 

 

 

 

 

 

Cap.

Cap.

Voltage

Voltage

Time

of Load

of Batt.

Initial

V

 

X

 

X

 

--

V

X

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st

V

 

X

 

X

 

--

V

X

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd

V

 

X

 

X

 

--

V

X

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3rd

V

 

X

 

X

 

--

V

X

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4th

V

 

X

 

X

 

--

X

V

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5th(Return)

V

 

X

 

X

 

--

V

X

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Overload)

V

 

X

 

X

 

V

--

--

--

--

--

--

--

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“V” : light up,

“X” : go out,

 

“--“ : not available

 

 

 

 

 

 

 

Battery mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select SW

UPS Status Display

 

Capacity Display

 

Digital Value Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

Load

Battery

Input

Output

Run

%

%

 

 

 

 

 

 

 

 

Cap.

Cap.

Voltage

Voltage

Time

of Load

of Batt.

Initial

X

 

V

 

--

 

--

X

V

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st

X

 

V

 

--

 

--

X

V

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd

X

 

V

 

--

 

--

V

X

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3rd

X

 

V

 

--

 

--

X

V

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4th

X

 

V

 

--

 

--

X

V

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5th(Return)

X

 

V

 

--

 

--

X

V

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press >3sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Sound

X

 

V

 

V

 

--

--

--

--

--

--

--

--

Disable)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press >3sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

again

X

 

V

 

X

 

--

--

--

--

--

--

--

--

(Sound Enable)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Overload)

X

 

V

 

--

 

V

--

--

--

--

--

--

--

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“V” : light up,

“X” : go out,

 

“--“ : not available

 

 

 

 

 

 

 

INPUT voltage meter: This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet. The UPS is designed, to continuously supply connected equipment with stable, 110/120 output voltage. In the event of a complete power loss, severe brownout, or over-voltage, the UPS relies on its internal battery to supply consistent 110/120 output voltage. The INPUT voltage meter can be used as a diagnostic tool to identify poor-quality input power.

OUTPUT voltage meter: This meter measures, in real time, the AC voltage that the UPS system is providing to the computer during normal line mode, and battery backup mode.

ESTIMATE RUN TIME: This displays the run time estimate of the UPS with the current battery capacity and load.

NORMAL icon: This icon appears when the UPS is working under normal conditions.

BATTERY icon: During a severe brownout or blackout, this icon appears and an alarm sounds (two short beeps followed by a pause) to indicate the UPS is operating from its internal batteries. During a prolonged brownout or blackout, the alarm will sound continuously. The BATT.CAPACITY meter will show one 20% capacity segment remaining to indicate the UPS's batteries are nearly out of power. You should save files and turn off your equipment immediately.

OVER LOAD icon: This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the overload, unplug some of your equipment from the battery-supplied outlets until the icon turns off and the alarm stops.

BATT. CAPACITY meter: This meter displays the approximate charge level, in 20% increments, of the UPS’s internal battery. During a blackout or severe brownout, the UPS switches to battery power, the BATTERY icon appears, and the charge level decreases.

LOAD CAPACITY meter: This meter displays the approximate output load level, in 20% increments, of the UPS’s battery outlets

REPLACING THE BATTERY

Replacement of batteries located in an OPERATOR ACCESS AREA.

1.When replacing batteries, replace with the same number of the following battery: BP8-12 / BB for CP685AVRLCD-G; HR1234W / BB for CP825AVRLCD-G.

2.CAUTION! Risk of Energy Hazard, 12 V, maximum 8(BP8-12 for CP685AVRLCD-G) and 9(HR1234W CP825AVRLCD-G) Ampere-hour battery. Before replacing batteries, remove conductive jewelry such as chains, wrist watches, and rings.

3.CAUTION! Do not dispose of batteries in a fire. The batteries may explode;

Image 1
Contents Installing Your UPS System Important Safety WarningsDefinitions for Illuminated Indicators Basic OperationTechnical Specifications Trouble ShootingCyberpower Greenpower UPS Technology Expected Runtime in Minutes