CPS1250AVR
Guaranteed Uninterruptible Power System
As the battery discharges, the unit will beep more rapidly, indicating that the battery is nearing discharge. Once the test is complete, plug the UPS back in to the AC outlet and start your computer. Please allow 4 hours for the UPS to recharge before attempting another
DEFINITIONS FOR ILLUMINATED LED INDICATORS
Power | Wiring | AVR | Using | Check | Circuit | Alarm | Condition |
Fault |
| Batter | Battery | Breaker |
|
| |
On |
|
|
| ||||
|
| y |
|
|
|
| |
On | Off | Off | Off | Off | Set | Off | Normal |
On | Off | Flash | Off | Off | Set | Off | AVR- AVR is maintaining a consistent 120v level (±5%) |
|
|
|
|
|
|
| during a power sag. |
ON | Off | On | Off | Off | Set | Off | AVR- AVR is maintaining a consistent 120v (±5%) |
|
|
|
|
|
|
| during a power surge |
Off | On/Off | Off | On | Off | Set | Two Beeps | Utility Failure- The UPS is providing battery power to |
|
|
|
|
|
|
| the |
Off | On/Off | Off | On | Off | Set | Rapid Beeps | Utility Failure- The UPS is providing battery power. |
|
|
|
|
|
|
| The rapid beeps indicate the battery will run out of |
|
|
|
|
|
|
| charge within a few minutes. |
Off | Off | Off | On | Off | Up | Two beeps or rapid | Overload- Occurs in the |
|
|
|
|
|
| beeps | Outlets. Turn the UPS off and unplug at least one |
|
|
|
|
|
|
| piece of equipment from the UPS. Wait 5 seconds, |
|
|
|
|
|
|
| reset the circuit breaker and turn the UPS on. |
On/Off | On/Off | On/Flash/Off | On/Off | Off | Set | Long Beep | Overload- Occurs in the |
|
|
|
|
|
|
| Outlets. Turn the UPS off and unplug at least one piece |
|
|
|
|
|
|
| of equipment from the UPS. Wait 5 seconds, reset the |
|
|
|
|
|
|
| circuit breaker and turn the UPS on. |
Off | Off | Off | On | Off | Up | Long Beep | Overload- Occurs in the |
|
|
|
|
|
|
| Outlets. Turn the UPS off and unplug at least one piece |
|
|
|
|
|
|
| of equipment from the UPS. Wait 5 seconds, reset the |
|
|
|
|
|
|
| circuit breaker and turn the UPS on. |
On | On/Off | On/Flash/Off | Off | On | Set | None | Weak Battery- Recharge the battery for at least 8 |
|
|
|
|
|
|
| hours. If Check Battery is illuminated contact |
|
|
|
|
|
|
| CyberPower Systems for battery replacement |
|
|
|
|
|
|
| information. |
Off | Off | Off | Off | Off | Set | Off | Surge Protection Malfunction- Lightning induced |
|
|
|
|
|
|
| power line surge has damaged the |
|
|
|
|
|
|
| function. Please contact CyberPower Systems |
On/Off | On/Off | On/Flash/Off | Flash | Flash | Set/Up | Off | Scheduled |
|
|
|
|
|
|
| flashing in rotation, the UPS is waiting to turn on as |
|
|
|
|
|
|
| configured in the schedule. |
On/Off | On/Off | On/Flash/Off | Flash | Flash | Set/Up | Three Beeps | Cold Start Disabled- If the two battery indicators are |
|
|
|
|
|
|
| flashing at the same time, the |
|
|
|
|
|
|
| disabled. The UPS will not start in the absence of AC |
|
|
|
|
|
|
| power. |
On/Off | On | On/Flash/Off | On/Off | On/Off | Set/Up | None | Electrical Wiring Fault- This indicates a wiring a |
|
|
|
|
|
|
| problem such as a bad ground, missed ground or |
|
|
|
|
|
|
| reversed wiring within the AC outlet. User is advised |
|
|
|
|
|
|
| to disconnect all electrical equipment from the outlet and |
|
|
|
|
|
|
| have the outlet checked by an electrician. |