Analog I/O Modules Calibration
Analog input/output modules are calibrated when you receive them. However, calibration is sometimes required. No screwdriver is necessary because calibration is done in software with calibration parameters stored in the
The
6.1Analog input module calibration
Modules: ADAM-5017, 5017H, 5018
1.Apply power to the
2.Assure that the module is correctly installed and is properly configured for the input range you want to calibrate. You can do this by using the ADAM utility software.
3.Use a precision voltage source to apply a span calibration voltage to the module‘s V0+ and V0- terminals. (See Tables
Figure 6-1: Applying calibration voltage
4.Execute the Zero Calibration command (also called the Offset Calibration command).