The following
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Common) D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each ABCD connector in the system MUST be wired consistently. NOTE: Improper wiring of the ABCD connector will cause the Evolution System to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on power.
III.INSTALL COMPONENTS
INSTALL NETWORK INTERFACE MODULE — Plan wire routing before mounting. The Evolution Network Interface Mod- ule is designed so that wires can enter it from the sides.
1.Remove top cover and mount NIM to wall using screws and wall anchors provided.
IV. VENTILATOR (HRV/ERV) WIRING
HRV / ERV INSTALLATION — The NIM can control a Bryant Heat Recovery Ventilator / Energy Recovery Ventilator (HRV / ERV). Connect four wires from ventilator control board (see ventilator installation instructions for details) to connector labeled (YRGB). This label identifies the color of the wire to match the ventilator wire colors (Y=yellow, R=red, G=green, B=blue or black). See Fig. 2 for ventilator (HRV / ERV) connection.
NOTE: If system is zoned (contains an Evolution Damper Con- trol Module), the ventilator may be connected either directly to the Damper Control module or to the NIM. In either case, the Evolution Zone Control will properly discover the ventilator.
V. DUAL FUEL WITH 1-SPEED HEAT PUMP WIRING
DUAL FUEL INSTALLATION WITH
VI.
SYSTEM START-UP
Follow the system
LED INDICATORS
Under normal operation, the Yellow and Green LEDs will be on continuously (solid). If the NIM does not successfully communi- cate with the Evolution Control, the Green LED will not be on. If there are faults present, the Yellow LED indicator will blink a
STATUS CODE | DESCRIPTION |
16 = | Communication Failure |
45 = | Board Failure |
46 = | Low Input Voltage |
FUSE
A
24 VAC POWER SOURCE
The NIM receives its 24 VAC power from the indoor unit C and D terminals (via ABCD connector bus). In most applications, there is sufficient power (VA capacity) available from the indoor unit transformer to accommodate a ventilator and / or outdoor unit connection. No additional transformer is required.