Product Data Document
July 16, 2007 - Page
Bristol® ControlWave® Remote Ethernet I/O
With the
38.4KB serial RS 485. The wide range of module
I/O configurations brings exceptional flexibility to network diversity. Each module is designed and rated for harsh industrial environments, a perfect compliment to the ControlWave Process Automation Management Solution as well as our Network 3000 measurement and control system.
Features
•Open Modbus (Modbus TCP) Ethernet connectivity
•RS 485 Modbus RTU or Modbus ASCII
•
•Internal 24 V dc loop power minimizes wiring cost
•‘Hot Swap’ I/O module replacement
•10 – 30 V dc power input
•
•CSA, UL Class I, Div. 2 Groups
Specifications
All I/O
•Compact 4 ¾” W x 3 ¼” H x 4 1/8” D
•10 – 30 V dc power input
•1.2 Watt typical per module (48 mA @ 24 Vdc)
– varies by module and load
•Temperature:
•Humidity: 5 – 95%
•RS 485 port Master or Slave up to 38400 baud
– up to 32 nodes per line
•Up to 16,000 nodes per network
•10Base T at 10 Mbps Ethernet port
•1200 V RMS 1 minute isolation on Ethernet port
•ESD (Electro Static Discharge) withstand: 8KV
•Vibration meets IEC
1g for 10 Hz to 150 Hz
.5g for 150 Hz to 2000 Hz
The ControlWave Remote Ethernet I/O series con- sists of seven modules
ControlWave Discrete Input Module
•Number of inputs: 16
•Input source or sink: Configurable
•Input voltage: 12/24 V AC/DC
•Input resistance: 3.6 KΩ
•One High Speed Counter channel up to 2 KHz
•Scan rate: 2 mS
•Power: .75 watt
Remote Automation Solutions
Website: www.EmersonProcess.com/Remote