Emerson Process Management ControlWave Remote Ethernet I/O manual Product Data Document, Features

Page 1

Product Data Document

420DS-2b

July 16, 2007 - Page

Bristol® ControlWave® Remote Ethernet I/O

With the ever-increasing demand for distributed I/O architectures Bristol® ControlWave® Remote I/O modules, from Emerson Process Management, are the ideal solution to minimize installation cost. The compact DIN-rail mount modules provide an open connectivity through 10 Mbps Ethernet and

38.4KB serial RS 485. The wide range of module

I/O configurations brings exceptional flexibility to network diversity. Each module is designed and rated for harsh industrial environments, a perfect compliment to the ControlWave Process Automation Management Solution as well as our Network 3000 measurement and control system.

Features

Open Modbus (Modbus TCP) Ethernet connectivity

RS 485 Modbus RTU or Modbus ASCII

Easy-to-use ConfigTools software configuration

Internal 24 V dc loop power minimizes wiring cost

‘Hot Swap’ I/O module replacement

10 – 30 V dc power input

-30 to +70°C operating temperature range

CSA, UL Class I, Div. 2 Groups A-D, and CE approved

Specifications

All I/O

Compact 4 ¾” W x 3 ¼” H x 4 1/8” D

10 – 30 V dc power input

1.2 Watt typical per module (48 mA @ 24 Vdc)

– varies by module and load

Temperature: -30 to +70°C operating temperature range

Humidity: 5 – 95% non-condensing

RS 485 port Master or Slave up to 38400 baud

– up to 32 nodes per line

Up to 16,000 nodes per network

10Base T at 10 Mbps Ethernet port

1200 V RMS 1 minute isolation on Ethernet port

ESD (Electro Static Discharge) withstand: 8KV

Vibration meets IEC 68-2-6

1g for 10 Hz to 150 Hz

.5g for 150 Hz to 2000 Hz

The ControlWave Remote Ethernet I/O series con- sists of seven modules

ControlWave Discrete Input Module

Number of inputs: 16

Input source or sink: Configurable

Input voltage: 12/24 V AC/DC

Input resistance: 3.6 K

One High Speed Counter channel up to 2 KHz

Scan rate: 2 mS

Power: .75 watt

Remote Automation Solutions

Website: www.EmersonProcess.com/Remote

Image 1