QuickSpecs
Compaq ProLiant DL380 G2
Power Specifications
| Part Number | |
| Spare Kit | |
| Operational Input Voltage | 90 TO 264 | 
| Range (V rms) | 
 | 
| Frequency Range (Nominal) | 47 to 63 (50/60) | 
| (Hz) | 
 | 
| Nominal Input Voltage (Vrms) | 100 | 115 | 208 | 220 | 230 | 240 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Max Rated Output Wattage Rating | 431 | 415 | 403 | 398 | 398 | 398 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Nominal Input Current (A rms) | 5.8 | 5.0 | 2.7 | 2.5 | 2.4 | 2.3 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Max Rated Input Wattage Rating (Watts) | 571 | 563 | 548 | 541 | 541 | 541 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Max. Rated VA  | 583 | 575 | 559 | 552 | 552 | 552 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Efficiency (%) | 70 | 71 | 73 | 74 | 74 | 74 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Power Factor | 0.98 | 0.98 | 0.98 | 0.98 | 0.98 | 0.98 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Leakage Current (mA) | 0.31 | 0.36 | 0.65 | 0.69 | 0.72 | 0.75 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Maximum Inrush Current (A peak) | 50 | 50 | 50 | 50 | 50 | 50 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Maximum Inrush Current duration | 20 | 20 | 20 | 20 | 20 | 20 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
System Specifications
ProLiant DL380 Generation 2 Fully Configured
Up to 2 Processors, 6 Memory Slots, 6 Hard Drives, 3 PCI Slots, and 2 Hot Plug Power Supplies
| Nominal Input Voltage (Vrms) | 100 | 115 | 208 | 220 | 230 | 240 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Fully Loaded System Input Wattage (W) | 431 | 415 | 403 | 398 | 398 | 398 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Fully Loaded System Input Current (A rms) | 4.4 | 3.8 | 2.0 | 1.8 | 1.8 | 1.7 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Fully Loaded System Thermal (BTU- Hr) | 1435 | 1415 | 1376 | 1357 | 1357 | 1357 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Fully Loaded System VA  | 443 | 437 | 412 | 406 | 406 | 406 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| System Leakage with all power supplies loaded | 0.63 | 0.72 | 1.30 | 1.38 | 1.44 | 1.50 | 
| (mA) | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| System Inrush Current with all power supplies | 100 | 100 | 100 | 100 | 100 | 100 | 
| loaded (A) | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | |||
| Power cord requirements | Nema  | 
 | Option no./Spare no.: See Chart below | |||
| 
 | 
 | 
 | 
 | |||
| 
 | 
 | Option no./Spare no.:  | ||||
| 
 | 
 | 
 | 
 | B21 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
NOTES:
*To review typical system power ratings use the Active Answers Power Calculator which is available via the online tool located at URL: http://activeanswers.compaq.com/aaconfiguratorcode/
To drill down to calculators:
- Click on: "ProLiant Servers"
- Click on the Server of interest. Example: DL380 G2
- Click on: "Power Calculator" link. (You may need to scroll down to see it)
| DA - 10902 Worldwide — Version 50 — September 30, 2003 | Page 34 |