QuickSpecs
HP ProLiant DL585 Generation 2 (G2)
Power Specifications
Part number |
|
|
|
|
|
|
|
| |
Operational Input Voltage Range | 90 to 264 |
|
|
|
|
|
|
| |
(Vrms) |
|
|
|
|
|
|
|
|
|
Frequency Range (Nominal) (Hz) | 47 to 63 (50/60) |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Nominal Input Voltage (Vrms) | 100 |
| 115 | 208 |
| 220 |
| 230 | 240 |
Max Rated Output Wattage Rating | 910 |
| 910 | 1300 |
| 1300 |
| 1300 | 1300 |
Nominal Input Current (A rms) | 11.9 |
| 10.2 | 7.7 |
| 7.3 |
| 6.9 | 6.6 |
Max Rated Input Wattage Rating (Watts) | 1163 |
| 1148 | 1566 |
| 1566 |
| 1548 | 1548 |
Max. Rated VA | 1186 |
| 1172 | 1598 |
| 1598 |
| 1579 | 1579 |
Efficiency (%) | 80 |
| 81 | 83 |
| 83 |
| 84 | 84 |
Power Factor | 0.98 |
|
|
|
| 0.98 |
| ||
Leakage Current (mA) | 0.43 |
| 0.50 | 0.90 |
| 0.96 |
| 1.00 | 1.04 |
Max. Inrush Current (A peak) | 100 |
| 100 | 100 |
| 100 |
| 100 | 100 |
Max. Inrush Current duration (mS) |
|
|
|
| 10 |
|
|
|
NOTE: – To review typical system power ratings use the Active Answers Power Calculator which is available via the online tool
located at url: http://h30099.www3.hp.com/configurator/powercalcs.asp To drill down to calculators:
Click on: "ProLiant Servers"
Click on the Server of interest. Example: DL585 G2
Click on: "Power Calculator" link. (You may need to scroll down to see it)
There are certain
Standard Rack Model | Description |
|
Power Cords / Jumper |
|
|
| ||
Cords |
| |
|
| |
Optional Country Power | Description | Option Kit Part |
Cords and Jumper Cords |
| Number |
| Nema | |
| Nema | |
| Nema | |
| ||
| ||
| ||
| ||
|
DA - 12575 Canada — Version 37 — May 28, 2008 | Page 40 |