FieldServer FS-8700-133 instruction manual Client Side Connection Descriptions

Page 6

FS-8700-133 Genisys Manual

Page 6 of 13

 

 

4.2Client Side Connection Descriptions

Section Title

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Column Title

 

Function

 

 

 

 

 

Legal Values

 

Port

 

 

Specify which port the device is connected to the

 

 

 

 

FieldServer

 

 

 

 

 

P1-P81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protocol

 

Specify protocol used

 

 

 

 

Genisys

 

 

 

 

 

 

 

 

 

 

 

 

Baud*

 

 

Specify baud rate

 

 

 

 

300 ,600, 1200, 2400, 4800, 9600 (Vendor

 

 

 

 

 

 

 

limitation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parity*

 

 

Specify parity

 

 

 

 

 

None, Even, Odd (Vendor limitation)

 

 

 

 

 

 

 

 

 

 

 

 

Data_Bits*

 

Specify data bits

 

 

 

 

8 (Vendor limitation)

 

 

 

 

 

 

 

 

 

 

 

 

Stop_Bits*

 

Specify stop bits

 

 

 

 

1, 2 (Vendor limitation)

 

 

 

 

 

 

 

 

 

 

 

 

Handshaking*

 

Specify hardware handshaking

 

 

 

None

 

 

 

 

 

 

 

 

 

 

 

 

Poll_Delay*

 

Time between internal polls

 

 

 

0-32000 seconds, 0.05 seconds

 

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

//

 

 

 

 

 

 

 

 

 

 

// Client Side Connections

 

 

 

 

 

 

 

//

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

Port

,Baud

,Data_Bits

,Stop_Bits

,Parity

,Protocol

 

 

 

 

P1

,9600

,8

,1

,None

,Genisys

 

 

 

 

 

 

 

 

 

 

 

 

 

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 6
Contents Driver Manual FS-8700-133 Genisys Table of Contents Genisys Description Driver Scope of SupplySupplied by FieldServer Technologies for this driver Hardware Connections Configuring the Fieldserver AS a Genisys Client Data Arrays/DescriptorsClient Side Connection Descriptions Client Side Node Descriptors OFF, onDriver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example Read Indications Map Descriptor Example Write Controls Configuring the Fieldserver AS a Genisys Server Appendix A. Advanced Topics Appendix A.1. Storage Structure for Data Type Bit and ByteAppendix B. Error Messages