FieldServer FS-8700-104 Configuring the FieldServer as a ControlNet Server, ControlNet Settings

Page 6

FS-8700-104_ControlNet_X30 Manual

Page 6 of 13

4.Configuring the FieldServer as a ControlNet Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver CD).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a ControlNet Client/Scanner.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for ControlNet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1.ControlNet Settings

Section Title

 

 

FieldServer

 

 

Column Title

Function

Legal Values

System_Station_Address*

ControlNet MAC ID of the FieldServer

1-99

Note:

The ControlNet MAC ID can also be set via the two rotary switches on the side of the FieldServer. These switches should be set to zero or to the same value as

System_Station_Address in the configuration file. Alternatively the System_Station_Address parameter should be eliminated from the configuration file. Failing to do so, will cause a warning LED to flash although the MAC ID from the configuration file will still be used.

Example

// FieldServer

 

FieldServer

 

Title,

System_Station_Address

CN_Test,

5

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 6
Contents FS-8700-104 ControlNet X30 Driver Table of Contents Max Nodes Supported FieldServer Mode Comments ControlNet X30 DescriptionFS-8700-104ControlNetX30 Manual FieldServer Technologies Description Hardware Connections Hardware Connection Tips / HintsSection Title Configuring the FieldServer as a ControlNet ServerControlNet Settings Column Title Function Legal ValuesServer Side Connection Descriptors Server Side Node DescriptorsDriver Specific Map Descriptor Parameters BoolMap Descriptor Example LED 3 LED Channel B Color Frequency Description LED 1 Module status Color Frequency DescriptionLED 2 LED Channel a Color Frequency Description LED 4 Module Owned Color Frequency DescriptionAppendix A.3. Using RSLogix 5000 for network configuration FS-8700-104ControlNetX30 Manual Channel LEDs DescriptionFS-8700-104ControlNetX30 Manual Appendix B.2. Using the Network Access Port

FS-8700-104 specifications

The FieldServer FS-8700-104 is a versatile communication gateway specifically designed for building automation and industrial control systems. This device is pivotal for integrating disparate systems, providing seamless connectivity across various protocols and platforms. One of the standout features of the FS-8700-104 is its ability to support a wide range of communication protocols, such as BACnet, Modbus, LonWorks, and OPC, making it suitable for diverse applications in smart buildings and industrial environments.

Equipped with robust hardware, the FS-8700-104 boasts a powerful processor that ensures efficient data handling and processing. Its compact design allows for easy installation in both new and existing infrastructures without requiring extensive modifications. The device comes with multiple communication ports, including Ethernet for high-speed connectivity and serial ports for older equipment integration. This flexibility makes it an ideal solution for bridging the gap between legacy systems and modern IoT devices.

The FS-8700-104 features an intuitive web-based interface, simplifying configuration and management. Users can easily set up communication mappings, monitor data traffic, and troubleshoot connectivity issues through this user-friendly platform. The device also supports extensive logging capabilities, allowing for the tracking of performance metrics and data trends over time, which is crucial for optimizing system performance and ensuring reliability.

In terms of security, the FS-8700-104 adheres to the latest industry standards, incorporating encryption protocols to protect sensitive data during transmission. This feature is increasingly important as building automation systems become more interconnected and vulnerable to cyber threats. Furthermore, the device is designed for high scalability, enabling users to expand their systems without the need for significant new investments.

Overall, the FieldServer FS-8700-104 is a powerful and flexible gateway that meets the evolving needs of modern building and industrial automation. Its extensive protocol support, robust hardware, user-friendly interface, and strong security measures make it an invaluable tool for integrating various systems and optimizing operational efficiency. Whether used in commercial buildings, manufacturing facilities, or critical infrastructure, the FS-8700-104 stands out as a reliable solution to facilitate smart technology adoption and enhance system interoperability.