FieldServer FS-8707-06 Example Setup Sample FieldServer Setup, Daatest, Smt, SDAAIUINT16 Rdbc

Page 11

FS-8707-06 FST OPC Server for FieldServers

Page 11 of 15

8.Example Setup

8.1.Sample FieldServer Setup

In this example, the low level driver (Modbus) is irrelevant to the operation of the OPC Server, however the user needs to be aware of how field addresses map to Data Array addresses.

FieldServer

Title,

DAA_TEST

// Server Side Connections

connections

adapter,

protocol

 

 

 

 

 

 

n1,

SMT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

 

 

 

 

SDA_BUA900_40001,

UInt16,

200

 

 

 

 

 

 

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

Node_Name,

Node_ID,

Protocol,

Retries,

Port

 

 

 

BUA900,

31,

Modbus_RTU,

8,

R2

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Address,

Length,

Scan_Interval

CMD_AI_BUA900_1,

SDA_AI_UINT16,

00,

RDBC,

BUA900,

40001,

100,

5s

CMD_AI_BUA900_2,

SDA_AI_UINT16,

100,

RDBC,

BUA900,

40101,

100,

5s

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 11
Contents FS-8707-06 FST OPC Server for FieldServers Table of Contents OPC Version Supported FST OPC Server for FieldServers DescriptionFieldServer Technologies Description Hardware Connections Installing the FST OPC Server for FieldServers Quick Start Steps to Implement a simple OPC configuration OPC datatypes FS-8707-06 FST OPC Server for FieldServers FS-8707-06 FST OPC Server for FieldServers SDAAIUINT16 Rdbc Example Setup Sample FieldServer SetupDaatest SMTExample OPC Server Setup Clsid Appendix A. Troubleshooting Appendix A.1. FAQSpeed limitations? Appendix A.2. The OPC Server Limitations- Q&AThis page Intentionally Left Blank