FieldServer FS-8707-06 Appendix A.2. The OPC Server Limitations- Q&A, Speed limitations?

Page 14

FS-8707-06 FST OPC Server for FieldServers

Page 14 of 15

Appendix A.2. The OPC Server – Limitations- Q&A

Q:How many fieldServers can one OPC Server communicate with?

A:Unlimited

Q: How many Clients can connect to the Server and how many points are possible?

A:Unlimited Clients & points, memory usage is about 2k/point/Client e.g.20 Clients with 10000 tags ea = 400MB. Server creates a thread for each Client, default each Client is looping thru 10000 tags every 25 ms looking for change of state. Such a config will probably flatten a 2G P4.

Q: Speed limitations?

A:The FS is the bottleneck at ~ 50 poll blocks/sec (to test set poll rate to 0)

e.g.. 2 FS total poll rate is ~100/s, if you have 10000 digitals in one DA on each FS that’s 2*50*10000 = 1 000 000 digitals per second.

Q: Remote Clients possible? Limits?

A:Yes I am running The Server & MB8PC under the debugger on my laptop, & Graphworx on another PC.

This is not recommended for complexity / reliability reasons.

Since the FieldServers are networked, rather run the Server on the Client machine - why bring a third layer in unnecessarily?.

When running remotely you should be able to OPC browse onto the Server machine, if this fails make sure that the OPCENUM service starts & runs on Server.

When running remotely the OPC Server is running under the app "dllhost.exe" in taskman. Because most Clients use OPC in asynchronous mode, the performance is almost indistinguishable for medium amounts of data.

Q:Is this an inprocess or out of process Server?

A:COM has 3 modes:- inprocess, local & remote

Local & remote have similar performance - the overhead of each COM call is 1000©s of times slower compared to inprocess.

Since this driver is capable of inprocess that should be used if option in your Client.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 14
Contents FS-8707-06 FST OPC Server for FieldServers Table of Contents FST OPC Server for FieldServers Description OPC Version SupportedFieldServer Technologies Description Hardware Connections Installing the FST OPC Server for FieldServers Quick Start Steps to Implement a simple OPC configuration OPC datatypes FS-8707-06 FST OPC Server for FieldServers FS-8707-06 FST OPC Server for FieldServers SMT Example Setup Sample FieldServer SetupDaatest SDAAIUINT16 RdbcExample OPC Server Setup Appendix A. Troubleshooting Appendix A.1. FAQ ClsidAppendix A.2. The OPC Server Limitations- Q&A Speed limitations?This page Intentionally Left Blank