5.CHANGE FLOW CONTROL NONE

6.CHANGE DEDICATED TCP xxx.xxx.xxx.xxx:2001U (where xxx... is the IP address of the Ether-ComTMconnected to the SCS-1 Receiver or PC running Remote Access+TM).

7.CHANGE AUTOSTART ENABLED

8.SHOW SERVER - Check and confirm the unit’s IP address, Subnet Mask and the Gateway address.

10.SHOW PORT - Check and confirm the speed, flow control, dedicated service, and autostart options are set correctly. (The unit is now ready to be connected to the 462N/862N with the cable provided with the ETHER-COM.)

11.LOGOUT

Important Note

Once the ETHER-COM has been configured in this manner, no local access is allowed through the serial port while the unit is connected to the network. To reconfigure the Ether-Com you must remove power from the unit, disconnect it from the network, and then reapply power. Press the Enter key within 10 seconds to enter the configuration mode. Enter the command FLUSH NVR to return the unit to its factory defaults. This erases all options including the IP address.

SCS-1 Receiver

The unit that connects to the SCS-1 Receiver is configured in the same manner with the exception of Dedicated Service.

The CHANGE DEDICATED option will not include any IP address, CHANGE DEDICATED TCP :2001U. This is necessary because the unit connected to the receiver will need to communicate with many different IP addresses.

Configuration for use with Remote Access+™ on a PC

This configuration is for applications where the Ether-Com server is used as the ethernet network interface for an IBM compatible PC on which is installed the DMP Remote Access™ software. The Remote Access program is used as a monitoring automation system and should be configured for HST Monitoring to allow it to process incoming alarm and system information from DMP panels installed on the same network.

HST Monitoring

The unit that connects to your PC running Remtoe Access+TM is configured in the same manner with the exception of Dedicated Service.

The CHANGE DEDICATED option will not include any IP address, CHANGE DEDICATED TCP :2001U. This is necessary because the unit connected to the receiver will need to communicate with many different IP addresses.

Ether-Com Programming