Minuteman UPS MBK-E SERIES Alarms On Battery, LOW Battery Warning, WEAK/BAD Battery, Overload

Page 11

English

ALARMS

ON BATTERY

When the UPS is operating on the batteries, the On-Battery LED will blink and the audible alarm will sound once every 10-seconds. The alarm will stop once the UPS returns to the On-Line operation.

LOW BATTERY WARNING

The UPS will sound two beeps every five-seconds when the battery reserve runs low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion.

WEAK/BAD BATTERY

The UPS automatically tests the battery’s condition and will illuminate the Weak/ Bad Battery LED and sound the alarm. This alarm will be repeated until the batteries pass a self test. If the battery is bad or disconnected, the Weak/Bad Battery LED will illuminate and the alarm will beep three times every five-min- utes until the battery is reconnected or replaced. If the battery is weak, the Weak/Bad Battery LED will illuminate and the alarm will beep one time every ten-minutes until the battery is recharged or replaced. It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a Weak/Bad Battery condition.

NOTE: If the UPS has a Weak/Bad Battery Alarm after reconnecting of replac- ing the batteries, the user must initiate a self test to clear the Weak/Bad Bat- tery Alarm. To initiate a self test see section 4 "SELF TEST".

OVERLOAD

When the amount of load attached to the UPS exceeds its power rating, the Overload LED will illuminate and the UPS will sound a constant alarm. This alarm will remain on until the excess load is removed or the UPS’s self protec- tion circuit shuts the UPS down.

UPS FAULT

When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will sound a constant alarm. The fault condition, in some instances, may be reset by turning the UPS OFF and then ON (see section 5 Troubleshooting).

FAN LOCK

AC Mode: If the fan becomes locked, the alarm will beep one time every two- seconds until the fan is unlocked.

Battery Mode: If the fan becomes locked, the alarm will beep one time every two-seconds for thirty-seconds, then the output will turn off, the alarm will sound continuously and the Fault LED will illuminate. The UPS must be turned off and the fan unlocked to clear the Fan lock Alarm.

COMMUNICATIONS PORT

The MBK-E series comes standard with a USB communication port.

NOTE: See the SentryII CD for the Power Monitoring Software installation. See the USB Driver CD for the USB installation.

10

Image 11
Contents MBK-E Series English Important Safety Instructions Authorized Service Personnel only Receiving Inspection English Rear Panel Connecting Your Equipment Installation PlacementInstallation Communications Port Connection Optional Connecting the UPS to AN AC SourceChecking the Site Wiring Fault Charging the BatterySelf Test DIP Switch SettingsTurning the Unit ON/OFF UPS Fault Alarms On BatteryLOW Battery Warning WEAK/BAD BatterySymptom Possible Cause What To Do Authorized Service Personnel only Replacing the BatteryBattery Replacement Procedure English Minuteman UPS If the UPS Requires ServiceEnglish UPS ID MBK-E English Limited Product Warranty Declaration of Conformity Robert CalhounEnglish English Do not print PN 34000227 Rev

MBK-E SERIES specifications

The Minuteman UPS MBK-E Series is engineered for the demanding environments of today’s digital world, providing reliable power protection for sensitive electronic systems. This series is particularly suited for applications in data centers, manufacturing facilities, and telecommunications, where downtime can result in significant financial loss.

One of the standout features of the MBK-E Series is its true online double conversion technology. This advanced technology ensures that connected equipment receives a consistent and clean power supply, free from disturbances such as voltage spikes, sags, and electrical noise. The UPS operates continuously, converting incoming AC power into DC power and then back to AC power, which results in a stable output, even during abnormal input conditions.

The MBK-E Series also includes a wide input voltage range, allowing the UPS to maintain operational capabilities even in fluctuating power environments. This feature is particularly valuable in regions with unreliable power infrastructure. Furthermore, the product is equipped with an advanced battery management system that extends battery life through intelligent charging methods, ensuring that critical systems remain powered during outages.

One of the notable characteristics of the MBK-E Series is its modular design. With an easily expandable capacity, users can customize their UPS systems to meet their specific needs, enabling straightforward upgrades as power demands grow. This flexibility helps organizations efficiently manage their investment in power protection.

In addition to its robust performance features, the MBK-E Series includes comprehensive monitoring and management options. Users can access real-time data regarding power conditions, battery status, and overall system health through an intuitive LCD interface. Remote management capabilities, often facilitated through SNMP or USB interfaces, allow for proactive monitoring and alerts, minimizing the risk of system failures.

The Minuteman UPS MBK-E Series is also designed with energy efficiency in mind, incorporating features such as eco-mode operation to reduce power consumption while maintaining critical functions. By lowering environmental impact and operational costs, this UPS series supports both sustainability and financial efficiency.

Overall, the Minuteman UPS MBK-E Series stands out for its reliability, performance, and flexibility, making it an excellent choice for businesses looking to safeguard their electronic devices and infrastructure against power interruptions. It embodies a blend of cutting-edge technology and user-friendly features, providing peace of mind in today’s power-sensitive landscape.