Distributed Intelligence in the GSSnet
The fi re detection control panel BCnet216 opens up ma- nifold possibilities for the realization of specifi c requests of fi re detection, especially in spacious buildings, high- rise buildings or
The decentralized security network that has been crea- ted by BCnet216 offers increased security and reduces the total expenses due to a much lower cabling volume. The consistent
A sectional control panel of the BCnet216 is parame- terised as main operating unit for the administration of the GSSnet, all other members can be equipped with or without a display and operating unit.
The system is designed modularly and can be gradually expanded according to future demands. The maximum size of a BCnet216 comprises 127 network members, 9700 detector zones, 9700 actuations, 999 alarming devices, 99 transmitting devices as well as 199 logic sectors. Different interfaces are available for the con- nection of external information devices, e.g., a facility management system or a remote maintenance sys- tem.
Cabling of the detectors is required only between two neighboring sectional control panels. This clear and flexible arrangement of the sectional control panel cre- ates a powerful network. In this way, most economical cabling and thus effi cient use of the installation expen- ses is guaranteed. Larger distances between individual sectional control panels can be bridged through the use of optical fi ber modems or long distance modems.
The entire virtual control panel BCnet216 provides for the monitoring in
BCnet sectional control panels are available in wall mount cabinets, as 19“ compact version and in 19“
Extinguishing Control System
If required, the BCnet216 can be easily expanded to an extinguishing control panel LCnet216 according to EN
The function of the extinguishing control panel is fully in- tegrated into the fi re detection control panel BCnet216, a combined operation is therefore possible.
The LCnet216 is certifi ed to EN
Optionally, the LCnet216 can be implemented with full hardware redundancy.
Specifications
Supply voltage | 21 – 30 VDC |
|
Current consumption at 24V | 140mA (without detectors) |
|
Idle loop current | typ. 300µA per detector/module |
|
Total loop current | max. 300mA (at reduced line resistance) |
|
Idle loop voltage | typ. 26V (Apollo/Discovery) or |
|
| typ. 29V (System Sensor/200), respectively |
|
Loop line resistance | max. 50Ω per core |
|
Number of ADM loops | 2 |
|
Number of detector zones | max. 128 per loop, max. 144 in total |
|
Ambient temperature |
| |
Dimensions W × H × D | 248 × 222 × 28 (mm) |
|
Weight | approx. 675g |
|
Part No. | 214034 |
|
Order name | BCnet Sectional Control Panel/Extension | A |