Configuring Automatic on Battery Shutdown

If set to Off (default), the load segment turns off only when commanded manually by the button, an external command, or through the display (Control > Load Segments).

If set to zero seconds (0s), the load segment turns off automatically when the UPS on Battery state activates.

If you select a value, the load segment turns off automatically after the selected delay while the UPS operates on battery, but the shutdown is cancelled if the utility returns before the delay has expired.

To set the shutdown times for each load segment:

1Press the button for one second to go to the main menu selection and scroll down to the Settings menu using the button.

2Press the button to enter the Settings menu.

3Use the button to scroll to the Automatic on Battery Shutdown option and press the button. The options display and the current settings flash when selected.

4Set the shutdown delay for one load segment using the and buttons.

5Press the button to confirm.

6Set the shutdown delay for the other load segment if applicable.

7Press the button to confirm.

Operation 51

Image 51
Contents Users Guide September 2009 164201789 Table of Contents Dell UPS Management Software RS-232 and USB Communication PortsUPS Status Menu Event Log Menu Testing BatteriesDell Online Rack UPS IntroductionIntroduction What are You Looking For? Find It Here Finding InformationUPS Output Power Safety WarningsSafety Warnings Safety Warnings Inspecting the Equipment InstallationUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet 208V Rear Panel Identifying the UPS Rear Panels230V Rear Panel Dell Online Rack UPS Front Panel Identifying the UPS Front PanelRemoving the Battery Retaining Bracket Rackmount SetupRemoving the Battery Trays Installing the Rails Installing the Cabinet Install the UPS battery trays see Figure Installation Installing the UPS Front Cover Installing the EBMInstalling Remote Emergency Power-off Installing the UPSRepo Connector Repo Connections Wire FunctionHardwiring the UPS Input Circuit Breaker Diagram UPS Initial Startup UPS Input Terminal Block UPS Wiring SpecificationsInstallation Operation UPS Startup and ShutdownStarting the UPS UPS Shutdown Starting the UPS on BatteryControl Button Functions Control Button Sequence Control Panel FunctionsChanging the Language Display FunctionsStartup Screen UPS Status Screen LockedUPS General Alarms Active Battery ModeBypass Mode Bad Battery Detected or Battery DisconnectedConverter Mode Status Summary Screens Description Battery Test StatusNormal Mode High Efficiency ModeEvent Log Battery Status Screens DescriptionMeasurements Control Screens Description Control ScreensIdentification Settings Description Available Settings Default Setting SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring the UPS Between Modes Transferring from Normal to Bypass ModeTransferring from Bypass to Normal Mode Setting Power StrategyBehavior on Overload Retrieving the Event LogControlling Load Segments Through the Display Configuring Load SegmentsConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring the UPS for an EBM Configuring Battery SettingsConfiguring Automatic Restart Running Automatic Battery TestsConfiguring Automatic Battery Tests RS-232 and USB Communication Ports Additional UPS FeaturesGND RS-232 Communication Port Pin AssignmentDell Network Management Card Dell Network Management Card OptionalDell UPS Management Software UPS Maintenance UPS and Battery CareTransporting the UPS Remove the UPS front cover see Figure Storing the UPS and Batteries When to Replace BatteriesUpdating the UPS Firmware Testing BatteriesSpecifications Regulation Battery mode Efficiency Normal modePower Levels Regulation Normal modeSafety Conformance Environmental and SafetyOperating Temperature Temperature Relative HumidityVoltage Battery ConfigurationBattery Type Battery RuntimesTroubleshooting Accessing Alarms and ConditionsUPS Status Menu Event Log Menu Typical Alarms and ConditionsAction Troubleshooting Troubleshooting Silencing the Alarm
Related manuals
Manual 8 pages 24.59 Kb

H952N, K804N, J739N, K805N, J730N specifications

The Dell J730N, K805N, J739N, 4200W, and 3750W are all high-performance server power supplies designed to provide reliable power solutions for various Dell server models. These power supplies are engineered to ensure maximum uptime, energy efficiency, and seamless operation in data center environments.

Starting with the Dell J730N, this power supply unit is known for its robust design and 730W output capacity. It features hot-swappable functionality, allowing for easy replacement without powering down the server. This is crucial for mission-critical applications where downtime can lead to significant operational challenges. The J730N is compatible with various Dell servers, making it a versatile choice for data centers looking to enhance their power management.

The K805N power supply is another excellent option with a power output of 800W. It incorporates advanced features such as Automatic Voltage Regulation (AVR), which ensures that the output voltage remains stable even during fluctuations in the input voltage. This technology is vital for protecting sensitive server components from potential damage caused by power inconsistencies. Additionally, the K805N is designed with a modular approach, allowing for easy integration and scalability.

The Dell J739N exemplifies Dell’s commitment to energy efficiency with its 750W rating. It meets stringent efficiency standards, making it an environmentally friendly option that helps reduce power consumption and operational costs. The J739N is often used in combination with other Dell equipment to create a cohesive and efficient power management strategy. Its reliability is bolstered by a combination of intelligent internal monitoring systems that detect and address power anomalies.

The 4200W and 3750W power supplies represent higher capacity options for larger, more demanding server environments. These units are equipped with multiple redundant power circuits, ensuring that if one circuit fails, others will continue to supply power without interruption. The advanced cooling technologies utilized in these models also enhance performance and reliability by preventing overheating.

Overall, these Dell power supplies reflect the highest standards in design and technology. They are integral to maintaining the health and efficiency of server operations, contributing significantly to the resilience and effectiveness of data-centered environments. With a focus on compatibility, energy efficiency, and reliability, the J730N, K805N, J739N, 4200W, and 3750W power supplies remain essential components in modern IT infrastructures.