MGE UPS Systems 1500C Maintenance, Troubleshooting, Indication Signification, Correction

Page 24

4.Maintenance

4.1Troubleshooting

If any of LEDs 12 , 13 or 14 flash, there is a operating anomaly or an alarm.

If a LED flashes, the bargraph data is no longer displayed.

Troubleshooting not requiring MGE UPS SYSTEMS after-sales support

Indication

Signification

 

 

LED 12 flashes and the

UPS overload. Overload is too long or too high.

buzzer beeps.

If AC power is present and within tolerances, the UPS

 

goes to bypass mode (supply directly by the AC-power

 

source). LED 20 flashes.

 

The buzzer beeps every seconds.

If AC power is not present or not within tolerances, the connected applications are no longer supplied. The buzzer sounds continuously.

LED 14 flashes.

A battery fault was detected during the automatic

 

battery test.

 

 

The yellow LED Ê15.

The function for monitoring the phase and neutral

flashes, the red indicator

position of your electrical network has detected a

light 10 behind the UPS

reversal.

comes on and the buzzer

 

sounds continuously.

 

Correction

Check the power drawn by the equipment and disconnect any non- priority devices.

Check that the battery connector is fully pushed in.

Replace battery module (see the Maintenance section).

Directly earthed neutral type networks: to correct cabling, unplug and turn the network socket, of the DIN-SCHUKO type, by 180 degrees or contact an electrician to modify your electrical network.

For all other network types, de- activate the detection function (this function is only operational for directly earthed neutral electrical networks):

Press for at least 5 seconds the pushbutton 9 behind the UPS (UPS stopped and connected to the network for less than 30 minutes).

Page 24 - 51031998EN/AA

Image 24
Contents Pulsar EXtreme CLAIntroduction Safety Safety rulesSafety of persons Product safetyUsing this document ForewordPictograms Contents Maintenance Presentation Pulsar EXtreme rangeTower model Rack modelBack Presentation Alarms Battery Ê Ê Ê Ê Ê Load Remaining Control panelInstallation Unpacking and checks2526 12 51031998EN/AA Installation of the rack version Connection to the RS 232 or USB communications port optional Installation of the communications-card option Battery connection Connecting the battery configuration to the UPSCurve C Max Cable and circuit-breaker not supplied 140 Curve C Max Cable and circuit-breaker not provided 140 UPS connection and settings Tower model Rack model Operation Start-upBargraph indications All connected equipment is energisedTransfer to battery power Threshold for the low-battery warningEnd of backup time Equipment connected to the UPS is supplied by the batteryBattery tab Personalisable function Default setting OptionsPersonalisation optional FunctionConnected equipment is no longer supplied with power Output tabBypass tab Maintenance TroubleshootingIndication Signification CorrectionIndication Signification Correction UPS recycling at the end of service life EnvironmentTechnical characteristics Simplified diagram Operating conditionsAppendices Input voltage and frequency Output voltage and frequencyGlossary UPS on / OFF via softwareIndex Connection5103199800-AA