Cleaning Switch

ICEU070A

Cleaning Switch

Located on the bottom side of the control box, it is used to energize the water inlet and the hot gas valves to fill the sump of the machine with water when needed.

Green Master Switch Push Button

Located in the front of the machine it’s used to switch ON and OFF the unit by pushing its green push button. When ON, its green light is ON.

Red Alarm/Re-Set Push Button

Located in the front of the machine (just beside the Master Switch) it works in conjunction with the Cleaning Remind Board and it’s activated when:

1. ON steady with machine in OFF mode

Condensing temperature is higher then 70oC or 158oF. (air cooled version)

2.Blinking twice and repeat with machine in OFF mode

Condenser sensor out of order.

3.ON steady with machine in ON mode Condenser air filter needs to be cleaned.

4.Slow blinking with machine in ON mode. Water system needs to be cleaned.

In the first case the machine can be Re-Set by pushing and holding the Red Alarm Re-Set Button for 5 seconds till the Red Light is OFF.

In the second case, first replace the condenser sensor then, push and hold the Red Re-Set Button for 5 seconds.

Cleaning Reminder PC Board

Located on the front left side of the machine, it works in conjunction with the condenser sensor and the Red Alarm Re-Set Push Button.

It consists of

￿Printed Circuit Board with a step down transformer (115V - 12V)

￿Relay

￿Dip Switch with two keys

￿Jumper for the set up of the Cut OFF/Alarm condensing temperature (70oC 158oF.- jumper OUT - for air cooled)

￿green four wire connector for power IN and

OUT

￿Red socket for the Water Level Sensor (future use)

￿Black socket for the Condenser Sensor and

￿White socket for the Red Alarm Re-Set Push Button

The main function of this PC Board is to switch the machine OFF when the condensing temperature is too high or signal the need for cleaning the condenser air filter or the water system. The time between the signal for the cleaning of the water system can be modified according to the setting of the two Dip Switches as below:

Time

1

2

1 Month

On

On

3 Months

Off

On

6 Months

On

Off

1 Year

Off

Off

Once the water system has been cleaned, push and hold the Red Alarm Re-Set Button for more then 20 seconds until it starts to blink. That will reset the control.

Condenser Air Filter

It is located in front of the air cooled condenser. It can be removed by pulling it through the opening in the front panel for cleaning or replacing. A lower plastic guide, installed inside the unit, is used for the correct sliding and location of the air filter.

Condenser Sensor

The condenser temperature sensor probe, located within the condenser fins detects the condenser temperature variations and signals them by supplying current, at low voltage, to the P.C.

BOARD.

In case the condenser temperature rises and reaches 70oC (160oF) – the control system will cause an immediate and total stop of the machine’s operation.