| ICEU070A | |
Service Diagnosis |
|
|
|
SYMPTOM | POSSIBLE CAUSE | SUGGESTED CORRECTION |
|
Unit will not run | Blown fuse | Replace fuse & check for cause of blown fuse. |
|
| Main switch in OFF position | Turn switch to ON position |
|
| Bin thermostat set improperly | Adjust rotating its setting screw |
|
| Loose electrical connections | Check wiring |
|
Red Alarm light ON | Too Hi Condensing | Reset the machine (Push & hold the Reset |
|
| Temperature | Button for 5 seconds) and check for reason why |
|
Red Alarm light Blinking | Condenser sensor out of order | Replace it and repeat |
|
Twice |
|
|
|
Compressor cycles | Low voltage | Check circuit for overloading |
|
intermittently |
| Check voltage at the supply to the building. If |
|
|
|
| |
|
| low, contact the power company |
|
| Purge the system |
| |
| Dirty condenser | Clean with vacuum cleaner, air or stiff brush. |
|
|
| (DO NOT use wire brush). |
|
| Air circulation blocked | Allow sufficient air space all around unit. |
|
| Compressor starting device | Check for loose wires in starting device. |
|
| loose wires |
|
|
Cubes too small | Cube size control set improperly | Check and adjust for proper operation. |
|
|
|
|
|
| Capillary tube partially restricted | Recover charge, add new gas & drier, after |
|
|
| evacuating system with vacuum pump. |
|
| Moisture in the system | Same as above. |
|
| Shortage of water | See remedies for shortage of water. |
|
| Shortage of refrigerant | Check for leaks & recharge. |
|
Cloudy cubes | Shortage of water | See remedies for shortage of water. |
|
| Dirty water supply | Use water softener or water filter. |
|
| Accumulated impurities | Use Ice Machine scale remover. |
|
Shortage of water. | Water spilling out through | Check or replace curtain. |
|
| curtain |
|
|
| Water solenoid valve not | Replace valve. |
|
| opening |
|
|
| Water leak in sump area | Locate and repair. |
|
| Water flow control plugged | Remove and clean. |
|
Page 12