MGE UPS Systems 18/280 kVA user manual Troubleshooting, Contact

Page 12

7. TROUBLESHOOTING

Malfunction

Solution

No neutral current is measured downstream

the filter.

No neutral current is measured upstream the

filter.

Tripping of the ‘Warning’ temperature sensor

of one of the chokes (Lo or Zo) (option).

Is the filter energised ?

Is breaker D1 closed ?

Is the filter feeding the distorting load ?

The CleanWave® filter reduces the neutral current by 10, approximately. It can happen that the remaining value is too low and is not measurable.

Temperature of the element has reached 165°C

The load must be reduced in order to avoid overheating of the filter.

Check that the phase and neutral currents respect the limits given in table 4.

Check that the ventilation grids (front and rear) are not obstructed.

Check that the Lo and Zo elements are not covered with dust.

Isn't the ambient temperature excessive (standard : 50°C) ?

Tripping of the "Alarm" temperature sensor of

Temperature of the element has reached 190°C

Danger ! The filter must immediately be switched

one of the chokes (Lo or Zo) (option).

 

off.

Table 11

If the observed malfunction is not in this list or if the problem remains after applying the recommended solutions, please contact MGE UPS SYSTEMS to the address below.

8. CONTACT

For any assistance or complementary information, please contact your local distributor MGE UPS SYSTEMS. You will find his details on the website www.mgeups.com .

MGE UPS SYSTEMS

CleanWave - Installation and user manual

Page 12/13

 

Version 2.1.4 – 15/01/2007 -

 

Image 12 Contents
CleanWave Index Introduction Presentation4/13 5/13 110 Safety CleanWave Electrical EngineeringInstallation and Starting CleanWave →Energised Maintenance Check that there is no voltage on the terminalsTroubleshooting Contact
Related manuals
Manual 13 pages 22.88 Kb