2.3.TECHNICAL SPECIFICATIONS
Standards |
|
|
|
|
|
|
Construction and safety : | ||||||
Conception : |
|
|
| |||
IP rating |
|
|
|
|
|
|
Unprotected : |
|
|
| IP00 | ||
Protected : |
|
|
| IP21 | ||
Electrical specifications |
| |||||
Frequency : |
|
|
| 50 / 60Hz | ||
Nominal voltage between phases : | 400V +15% / | |||||
Reduction ratio |
| INeutral upstream | 1:10 | |||
| INeutral downstream |
| ||||
Ratio | INeutral |
| : |
|
| ≤ 1.8 |
IPhase |
|
| ||||
|
|
|
|
| ||
Inrush current : |
|
|
| ≤ Inominal | ||
Overload capacity : | 10% - 1 hour | |||||
|
|
|
|
|
| 25% - 10 minutes |
|
|
|
|
|
| 50% - 2 minutes |
Insulation class : | 1.1 kV | |||||
Dielectric strength : | 3 kV | |||||
Thermal class of insulation: | H | |||||
Environmental conditions |
| |||||
Maximum ambient temperature : | 50°C | |||||
Maximum altitude : | 1000m | |||||
Maximum relative humidity : | 90% without condensation |
Please contact your MGE UPS SYSTEMS correspondent for different operating conditions.
→www.mgeups.com
MGE UPS SYSTEMS | CleanWave - Installation and user manual | Page 6/13 |
| Version 2.1.4 – 15/01/2007 - |
|