APC 990-3051C-001 Specifications, Input conductors, AC Input, AC Output, 200 A, 75C Conductors

Page 3

Specifications

Input conductors

This product is rated 200 A. It should be supplied with a circuit breaker with a maximum rating of 200 A.

For North America, if supplied by a 200 A circuit breaker, it is recommended that conductors are sized in accordance with Table 3.

For countries outside of North America, if supplied by a 200 A circuit breaker, it is recommended that conductors are sized in accordance with Table 4.

Note: Input conductors are to be torqued to 31.1 Nm

(275 lb-in) using a 8 mm (5/16 in) Allen (hexagonal) wrench.

Table 1

AC Input

Nominal voltage

400 V 3 PH

 

208 V 3 PH

Frequency

47-63 Hz

Voltage configuration

3 W + N + PE

Maximum upstream circuit breaker

200 A

Maximum continuous current

160 A

Maximum continuous current with

200A

100% rated circuit breaker

 

Maximum main input conductor size

250 mcm

 

 

Table 2

AC Output

Nominal voltage

230 V/400 V 3 PH

 

120 V/208 V 3PH

Maximum continuous current

200 A

Voltage configuration

3 W + N + PE or 3 x (1 W + N + PE),

 

based on attached APC Power

 

Distribution Modules

Full load rating

138 kW @ 400 V 3PH

 

72 kW @ 208 V 3 PH

Output power cable connections

Various, based on attached APC Power

 

Distribution Modules

Output power cable lengths

Various, based on attached APC Power

 

Distribution Modules

Maximum APC Power Distribution

6

Modules

 

Maximum power distribution poles

18

 

 

Table 3

200 A, 75°C Conductors

Wiring System

Copper

Aluminum

3 CCC, 30°C Ambient

Ø&N = 3/0 AWG

Ø&N = 4/0 AWG

 

G = 6 AWG

G = 4 AWG

4 CCC, 30°C Ambient

Ø&N = 4/0 AWG

Ø&N = (2) 1/0 AWG

 

G = 6 AWG

G = (2) 4 AWG

Notes

CCC= Current-Carrying Conductors AWG = American Wire Gauge

kcmils = MCM = Thousands of Circular Mils Ø = Phase conductor

N = Neutral conductor

G = Ground (Equipment Grounding) conductor

(2) = two conductors per terminal

Table 4

200 A, Conductors

 

 

Copper, XLPE

 

 

Aluminum,

 

Copper, PVC

or EPR

Aluminum,

XLPE or ERP

Install.

Insulation,

Insulation,

PVC Insulation, Insulation,

Method 30°C Ambient

30°C Ambient 30°C Ambient

30°C Ambient

B1

Ø&N = 95 mm²

Ø&N = 70 mm² Ø&N =

150 mm² Ø&N =

95 mm²

 

PE = 50 mm²

PE = 35 mm²

PE = 95 mm²

PE = 50 mm²

B2

Ø&N = 120 mm² Ø&N = 95 mm² Ø&N =

240 mm² Ø&N =

120 mm²

 

PE = 70 mm²

PE = 50 mm²

PE = 120 mm²

PE = 70 mm²

C

Ø&N = 95 mm²

Ø&N = 70 mm² Ø&N =

150 mm² Ø&N =

95 mm²

 

PE = 50 mm²

PE = 35 mm²

PE = 95 mm²

PE = 50 mm²

E

Ø&N = 95 mm²

Ø&N = 70 mm² Ø&N =

120 mm² Ø&N =

95 mm²

 

PE = 50 mm²

PE = 35 mm²

PE = 70 mm²

PE = 50 mm²

F

Ø&N = 70 mm²

Ø&N = 50 mm² Ø&N =

95 mm²

Ø&N =

70 mm²

 

PE = 35 mm²

PE = 25 mm²

PE = 50 mm²

PE = 35 mm²

Notes

Ø= Phase conductor N = Neutral conductor

PE = Protective Earth conductor PVC = Polyvinyl-chloride XLPE = Cross-linked polyethylene EPR = Ethylene propylene rubber

3

Image 3
Contents How to perform a Total Power Off InstallationInventory Enlarge the knock out hole for larger conduit Install input cablesInput cables Communication cablesAC Output SpecificationsInput conductors AC InputAPC Worldwide Customer Support Physical Dimensions, Environment and CompliancePhysical Dimensions Regulatory Agency Approval