Specifications
Input conductors
This product is rated 200 A. It should be supplied with a circuit breaker with a maximum rating of 200 A.
For North America, if supplied by a 200 A circuit breaker, it is recommended that conductors are sized in accordance with Table 3.
For countries outside of North America, if supplied by a 200 A circuit breaker, it is recommended that conductors are sized in accordance with Table 4.
Note: Input conductors are to be torqued to 31.1 Nm
(275 
Table 1
AC Input
Nominal voltage  | 400 V 3 PH  | 
  | 208 V 3 PH  | 
Frequency  | |
Voltage configuration  | 3 W + N + PE  | 
Maximum upstream circuit breaker  | 200 A  | 
Maximum continuous current  | 160 A  | 
Maximum continuous current with  | 200A  | 
100% rated circuit breaker  | 
  | 
Maximum main input conductor size  | 250 mcm  | 
  | 
  | 
Table 2
AC Output
Nominal voltage  | 230 V/400 V 3 PH  | 
  | 120 V/208 V 3PH  | 
Maximum continuous current  | 200 A  | 
Voltage configuration  | 3 W + N + PE or 3 x (1 W + N + PE),  | 
  | based on attached APC Power  | 
  | Distribution Modules  | 
Full load rating  | 138 kW @ 400 V 3PH  | 
  | 72 kW @ 208 V 3 PH  | 
Output power cable connections  | Various, based on attached APC Power  | 
  | Distribution Modules  | 
Output power cable lengths  | Various, based on attached APC Power  | 
  | Distribution Modules  | 
Maximum APC Power Distribution  | 6  | 
Modules  | 
  | 
Maximum power distribution poles  | 18  | 
  | 
  | 
Table 3
200 A, 75°C Conductors
Wiring System  | Copper  | Aluminum  | 
3 CCC, 30°C Ambient  | Ø&N = 3/0 AWG  | Ø&N = 4/0 AWG  | 
  | G = 6 AWG  | G = 4 AWG  | 
4 CCC, 30°C Ambient  | Ø&N = 4/0 AWG  | Ø&N = (2) 1/0 AWG  | 
  | G = 6 AWG  | G = (2) 4 AWG  | 
Notes
CCC= 
kcmils = MCM = Thousands of Circular Mils Ø = Phase conductor
N = Neutral conductor
G = Ground (Equipment Grounding) conductor
(2) = two conductors per terminal
Table 4
200 A, Conductors
  | 
  | Copper, XLPE  | 
  | 
  | Aluminum,  | |
  | Copper, PVC  | or EPR  | Aluminum,  | XLPE or ERP  | ||
Install.  | Insulation,  | Insulation,  | PVC Insulation, Insulation,  | |||
Method 30°C Ambient  | 30°C Ambient 30°C Ambient  | 30°C Ambient  | ||||
B1  | Ø&N = 95 mm²  | Ø&N = 70 mm² Ø&N =  | 150 mm² Ø&N =  | 95 mm²  | ||
  | PE = 50 mm²  | PE = 35 mm²  | PE = 95 mm²  | PE = 50 mm²  | ||
B2  | Ø&N = 120 mm² Ø&N = 95 mm² Ø&N =  | 240 mm² Ø&N =  | 120 mm²  | |||
  | PE = 70 mm²  | PE = 50 mm²  | PE = 120 mm²  | PE = 70 mm²  | ||
C  | Ø&N = 95 mm²  | Ø&N = 70 mm² Ø&N =  | 150 mm² Ø&N =  | 95 mm²  | ||
  | PE = 50 mm²  | PE = 35 mm²  | PE = 95 mm²  | PE = 50 mm²  | ||
E  | Ø&N = 95 mm²  | Ø&N = 70 mm² Ø&N =  | 120 mm² Ø&N =  | 95 mm²  | ||
  | PE = 50 mm²  | PE = 35 mm²  | PE = 70 mm²  | PE = 50 mm²  | ||
F  | Ø&N = 70 mm²  | Ø&N = 50 mm² Ø&N =  | 95 mm²  | Ø&N =  | 70 mm²  | |
  | PE = 35 mm²  | PE = 25 mm²  | PE = 50 mm²  | PE = 35 mm²  | ||
Notes
Ø= Phase conductor N = Neutral conductor
PE = Protective Earth conductor PVC = 
3