Installation
Modular 
Distribution Unit
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the modular 
Handling Safety
Heavy: To prevent back injury, two or more people are required to install the PDU in a rack.
Electrical Safety
Warning: To reduce risk of electric shock or injury to persons, disconnect all sources of power before servicing.
Note: Install the unit in accordance with the National and Canadian Electrical Codes, and if applicable, local codes.
Note: To prevent arcing when removing an APC Power Distribution Module (PDM) from the PDU, set all PDMs to OFF. Do not remove the modules under load.
Inventory
Item  | Part Number | Quantity | 
  | 
  | |
Modular   | ||
200 A 400 V 18 Pole 5U  | and  | 
  | 
  | 
  | |
Literature kit   | 0L 1532  | 1  | 
Label kit   | 
  | |
Rail stationary black  | 2  | |
Rail adjustable black  | 2  | |
Tray support chassis   | 1  | |
Screw M6x12 phil flat head  | 6  | |
Nut M6 flanged hex  | 6  | |
Washer M6 black plastic cup  | 14  | |
Screw M6x16 phillips/slot  | 14  | |
Nut cage M6 14/16 swg  | 6  | |
Bracket   | 2  | |
Plate blank cover brain PCB  | 1  | |
  | 
  | 
  | 
How to perform a Total Power Off
1Set all the APC Power Distribution Modules (PDM) to the OFF position.
2Set the utility/mains circuit breaker to the OFF position.
3If the utility/mains is an UPS, set the UPS and its circuit breaker supplying this product to the OFF position.
4Disconnect the input conductors from the utility/mains or the UPS.
Installation
How to install the PDU
1Install the mounting rails in the enclosure by using the screws provided. The PDU requires a 5U space from the top of the enclosure.
1 ![]()
5 U
pdx0244a
2Slide the support tray into the mounting rails and secure it with the screws provided.
2
pdx0240a
3Slide the PDU on to the support tray and secure it to the front posts of the enclosure with the screws provided.
4Slide the bracket 
3  | 4  | 
pdx0242a
12/2009  |