5:STORAGE AND MAINTENANCE

Storage

Store the UPS covered in a cool, dry location, with the battery fully charged.

At -15 to +30 ° C (+5 to +86 ° F), charge the UPS battery every six months.

At +30 to +45 ° C (+86 to +113 ° F), charge the UPS battery every three months.

Battery Replacement

The UPS battery life differs based on usage and environment. Consider replacing the battery every three years.

This UPS has an easy to replace, hot-swappable battery. Replacement is a safe procedure, isolated from electri- cal hazards. You may leave the UPS and connected equipment on during the replacement procedure. See your dealer or contact APC (see Contact Information) for information on replacement batteries.

Note: Upon battery disconnection, equipment is not protected from power outages.

For battery replacement instruction, refer to applicable steps in Rack-Mounting.

Be sure to deliver the spent battery to a recycling facility or ship it to APC in the replacement battery packing material.

9

Image 11
Contents APC Smart-UPSSC Page Position the UPS IntroductionUnpack Rack-Mounting Tower Configuration Wall Mounting Start the UPS Connect Equipment to the UPSConnect the UPS to the Network if Applicable Front Display Panel User Configurable Items 110/120 V model Storage Battery ReplacementTROUBLESHOOTING, SHIPPING, and Service Replace Battery LED is Illuminated Shipping and Service Regulatory and Warranty Information Limited Warranty