4:STORAGE, MAINTENANCE, AND TRANSPORTING

Storage

Store the UPS covered and flat (rack mount orientation) in a cool, dry location, with the batteries fully charged.

At -15 to +30 ° C (+5 to +86 ° F), charge the UPS battery every six months.

At +30 to +45 ° C (+86 to +113 ° F), charge the UPS battery every three months.

Replacing the Battery Module

This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on for this proce- dure. See your dealer or contact APC at the web site, www.apc.com/support for information on re- placement battery modules.

Once the battery is disconnected, the connected equipment is not protected from power outages.

Refer to Installing the Batteries, in this manual.

Reverse the instructions for battery removal. Note: Pull the front battery out of the UPS by pull- ing the clear label, not the white cord.

Be sure to deliver the spent battery to a recycling facility or ship it to APC in the replacement battery packing material.

REMOVING THE UPS FROM THE RACK

Step B

Step A

8

Image 10
Contents Smart-UPS Page Unpacking InstallationIntroduction Positioning the UPSInstalling the Batteries Hardwire the Electrical Connection 230V Models OnlyMounting the UPS in the Rack Connecting Equipment and Power to the UPS Pack model number for your UPSOperation On Battery Operation Optional External Battery PacksUser Configurable Items UPS ID UpsidenMin STORAGE, MAINTENANCE, and Transporting Replacing the Battery ModuleStorage Troubleshooting UPS will not Turn OFFMent from the UPS to eliminate the overload Service Regulatory Agency Approvals and Radio Frequency Warnings Regulatory and Warranty InformationDeclaration of Conformity