NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT
ACCESSORY CARDS.
FUNCTION | FACTORY | USER SELECTABLE |
| DESCRIPTION | ||||||
DEFAULT |
|
| CHOICES |
| ||||||
|
|
|
|
| ||||||
Low Battery Warning. |
|
|
| Brightly lit: Low battery | The low battery warning | |||||
| 2 min. |
| ||||||||
PowerChute interface |
|
| warning interval is about | beeps are continuous when | ||||||
|
|
| ||||||||
|
|
| two minutes. | less than 7 minutes of run | ||||||
|
|
| ||||||||
software provides auto- |
|
|
| |||||||
|
|
| Dimly lit: Low battery | time remain. | ||||||
matic, unattended shut- |
|
|
| |||||||
|
|
| warning interval is about | To change the warning inter- | ||||||
down when approximately |
|
|
| |||||||
|
|
| five minutes. | |||||||
two minutes (by default) of |
|
|
| val default setting, press the | ||||||
|
|
| Off: Low battery warning | |||||||
battery operated run time |
|
|
| voltage sensitivity button | ||||||
|
|
| interval is about seven | |||||||
remains. |
|
|
| while pressing and holding | ||||||
|
|
| minutes. | |||||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| the | button. |
|
|
|
|
|
| 2 min. |
|
| ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 5 min. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 5 min. |
|
|
|
|
|
|
|
|
|
| 7 min. |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
Synchronized | 0 seconds | 60, 180, 300 seconds | The UPS will wait the speci- | |||||||
Delay |
|
|
|
|
|
|
|
| fied time after the return of | |
|
|
|
|
|
|
|
|
| utility power before | |
|
|
|
|
|
|
|
|
| (to avoid branch circuit over- | |
|
|
|
|
|
|
|
|
| load). |
|
|
|
|
|
|
|
|
|
|
| |
High Transfer Point | 230V models: | 230V models: | To avoid unnecessary battery | |||||||
| 253VAC | 264, 271, 280VAC | usage, set the high transfer | |||||||
| 208V models: | 208V models: | point higher if the utility volt- | |||||||
| age is chronically high and | |||||||||
| 229VAC | 234, 239, 224VAC | ||||||||
| the connected equipment is | |||||||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| known to work under this | |
|
|
|
|
|
|
|
|
| condition. | |
|
|
|
|
|
|
|
|
|
| |
Low Transfer Point | 230V models: | 230V models: | Set the low transfer point | |||||||
| 196VAC | 188, 204, 208VAC | lower if the utility voltage is | |||||||
| 208V models: | 208V models: | chronically low and the con- | |||||||
| nected equipment can tolerate | |||||||||
| 177VAC | 182, 168, 172VAC | ||||||||
| this condition. | |||||||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
7