American Power Conversion 60-80kW 208/480V manual Alarms and Events, Displaying the Alarm Stack

Page 24

Alarms and Events

5.0 Alarms and Events

Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise.

Certain alarms, such as battery alarms, need resetting. See section 4.0 Parameter Settings.

All alarms are also registered in an event logger and remains there in a stack with room for 250 events. The events are stored in the same order as they arose - showing the latest first.

Besides the alarms the following operational modes are also stored in the event logger.

Mode

Comments

MPU is reset

UPS has been completely switched off

Stand-by

UPS has been in stand-by mode by parallel system

Normal operation

UPS has been in normal operation

Battery operation

UPS has been in battery operation

Bypass operation

UPS has been in bypass operation

System off

UPS has been off

5.1Displaying the Alarm Stack

Action

 

Description

1.

Press

 

Access to the alarm stack.

2.

Press

or

Scroll up or down through the alarm stack

 

 

 

messages.

 

 

 

Last message is "No (further) alarm".

3.

Press

 

Exits the alarm stack. If not operated the system

 

 

 

will exit the alarm stack automatically after 30

 

 

 

seconds.

 

 

 

 

5.2Displaying the Event Stack

Action

 

Description

1.

Press

and

Press the two keys simultaneously to get access

 

 

 

to the events stack

2.

Press

or

Scroll up or down through the event stack

 

 

 

(last message is "No (further) event").

3.

Press

 

Displays the time where the event happened.

4.

Press

 

Exits the event stack. If not operated the system

 

 

 

will exit the event stack automatically after 30

 

 

 

seconds.

 

 

 

 

990-4035

24

User Guide APC Silcon 60-80kW 208V/480V UPS

Image 24
Contents APC Silcon 60-80kW 208/480V UPS User Guide Copyright 2000 APC Denmark ApSSafety Symbols used in this manual User Guide APC Silcon 60-80kW 208V/480V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Stop UPS for complete power down Switching off the UPSStart UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Display of Measured Values Batt. load Batt. tankUsing the Remote Display Economy ModeParameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsPossible Alarms Alarms Description ActionUnlock Rectifying Alarm Messages Parallel Operation Alarms Correction of false alarm situations during serviceMaintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC DenmarkUser Guide APC Silcon 60-80kW 208V/480V UPS User Guide APC Silcon 60-80kW 208V/480V UPS