LEDs and Audible Alarms

The on-line LED illuminates when the UPS is supplying utility power to the loads.

On Battery

During on-battery operation, the on-battery LED illuminates and the UPS sounds an audible alarm consisting of four beeps every 30 seconds. The alarm stops when the UPS returns to on-line operation.

Overload

When the UPS is overloaded (when the connected loads exceed the maximum specified in the “maximum load” listed in Specifications, page 9.), the overload LED comes on and the UPS emits a sustained tone. The alarm remains on until the overload is removed. Disconnect nonessential load equipment from the UPS to eliminate the overload.

Replace Battery

If the battery fails a self-test, the UPS emits short beeps for one minute and the replace battery LED illuminates. The UPS repeats the alarm every five hours. Perform the self-test procedure to confirm replace battery conditions. The alarm stops when the battery passes the self-test.

Function

 

 

LED

 

Tone

 

 

 

 

 

 

UPS is on

m

UPS is running on battery

m

4

UPS is performing self-test

m

X

Overload

m

1

Overload shutdown

m

1

Output short circuit

m

1

Transformer failure

m

1

Low Battery (while on battery)

m

1

Replace battery condition

m

2

Battery disconnected in self test

3

UPS internal alarms:

 

 

 

 

 

boost/trim failure

X

X

1

transfer relay weld

X

X

X

X

1

sleep mode

X

X

 

 

Key:

LED

 

Tone

— = irrelevant to condition

— = irrelevant to condition

m = on steady

1

= sustained tone

X = flashing

2

= 1 minute of beeping every 5 hours

• = Off

3 = fading tone

 

4

= 4 beeps every 30 seconds

990-5022A, Revision 2 6/99

6

Image 10
Contents 990-5022A, Revision 2 6/99 Connect Equipment Install UPSTurn on UPS Table of Contents Page Electrical Safety SafetyHandling Safety Page Installation Initial Inspection990-5022A, Revision 2 6/99 Operating Instructions SetupBattery Pack Charge Computer Interface PortReplace Battery LEDs and Audible AlarmsOn Battery OverloadOperating Modes StorageReplacement Batteries Replacing the Battery PackBattery Pack Replacement Procedure Specifications ServiceLimited Warranty APC Japan Contact Information