4:USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

 

 

 

 

Automatic

Every 14 days

Every 7 days

Set the interval at which the UPS will

Self-Test

(336 hours)

(168 hours),

execute a self-test.

 

 

On Startup Only,

 

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight charac-

Uniquely identify the UPS, (i.e. server

 

 

ters (alphanumeric)

name or location) for network man-

 

 

 

agement purposes.

 

 

 

 

Date of Last

Manufacture Date

mm/dd/yy

Reset this date when you replace the

Battery

 

 

battery module.

Replacement

 

 

 

 

 

 

 

Minimum Capacity

0 percent

0, 15, 50, 90 percent

Specify the percentage to which batter-

Before Return from

 

 

ies will be charged following a low-

Shutdown

 

 

battery shutdown before powering

 

 

 

connected equipment.

 

 

 

 

Voltage Sensitivity

High

High sensitivity,

Note: In situations of poor power qual-

The UPS detects

 

Medium sensitivity,

ity, the UPS may frequently transfer to

 

Low sensitivity

battery operation. If the connected

and reacts to line

 

 

 

equipment can operate normally under

voltage distortions

 

 

 

 

such conditions, reduce the sensitivity

by transferring to

 

 

 

 

setting to conserve battery capacity

battery operation to

 

 

 

 

and service life.

protect connected

 

 

 

 

 

equipment.

 

 

 

 

 

 

 

Alarm Delay After

5 seconds

30 second delay,

Set the delay to avoid alarms for minor

Line Fail

 

At low battery

power glitches.

 

 

condition,

 

 

 

No alarm

 

 

 

 

 

Shutdown Delay

60 seconds

60, 180, 300, 600

Set the interval between the time when

 

 

seconds

the UPS receives a shutdown com-

 

 

 

mand and the actual shutdown.

 

 

 

 

Low Battery

2 minutes

2, 5, 7, 10 minutes

The UPS will beep when 2 minutes of

Warning

PowerChute

(Times are approxi-

battery runtime remains.

 

 

 

Business Edition

mate.)

Change the low battery warning inter-

 

software provides

 

val setting to the time that the operat-

 

automatic, unat-

 

ing system or system software requires

 

tended shutdown

 

to safely shut down.

 

when approxi-

 

 

 

mately 2 minutes

 

 

 

of battery oper-

 

 

 

ated runtime re-

 

 

 

mains.

 

 

 

 

 

 

 

 

7

 

Image 9
Contents APC Smart-UPSSC Page Introduction UnpackPosition the UPS Rack-Mounting Tower Configuration Wall Mounting Connect Equipment to the UPS Connect the UPS to the Network if ApplicableStart the UPS Front Display Panel User Configurable Items 110/120 V model Storage Battery ReplacementTROUBLESHOOTING, SHIPPING, and Service Replace Battery LED is Illuminated Shipping and Service Regulatory and Warranty Information Limited Warranty