APC SMC15002U, SMC10002U Feature Reference Guide, System Faults, Normal Mode, Configuration Mode

Page 11

System Faults

120 Vac

230 Vac

su0752a

su0752b

P00 Output Overload

P01 Output Short Circuit

P02 Output Over Voltage

P04 Unit Over Temperature

P06 AVR Relay Fault

P13 Inverter Fault

For more information on System Faults, contact customer support at the APC by Schneider Electric Web site, www.apc.com/support.

Feature Reference Guide

Normal Mode

Function

Button

Timing

UPS

Description

(seconds)

State

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the POWER ON/OFF button to turn on the UPS. The UPS

Power On

 

 

0.2

Off

will operate on AC power.

 

 

If AC power is not available the UPS will operate on battery

 

 

 

 

 

 

 

 

 

 

power.

 

 

 

 

 

 

Power Off

 

 

2

On

Press the POWER ON/OFF button to turn off the UPS.

 

 

 

 

 

 

 

 

Display

 

 

 

 

 

 

 

 

 

 

 

Status

 

 

0.2

On

Press to verify the status or condition of the UPS. The LCD

Inquiry

 

 

will illuminate for 60 seconds.

 

 

 

 

 

 

 

 

 

 

Mute

 

 

 

 

 

 

 

 

 

 

 

Enable/

 

 

2

On

Enable or disable the audible alarms. The Mute icon will

Disable

 

 

illuminate and the UPS will beep once.

 

 

 

 

 

 

 

 

 

 

Fault Reset

 

 

2

Fault

After a fault has been identified, press the POWER ON/OFF

 

 

 

 

button to remove the visual indication and return to standby

 

 

 

 

 

 

 

status.

 

 

 

 

 

 

Configuration Mode

The Configuration Mode provides additional options for the UPS. Press and hold the MUTE and

DISPLAY buttons for 2 seconds until the system emits a short beep and the display will flash to

indicate the UPS has entered Configuration Mode.

When in Configuration Mode the DISPLAY button forwards the display through the available options and the MUTE button toggles the configuration settings for that option.

Note: When system detects 15 seconds of no activity in Configuration Mode, or when you press and hold the MUTE and DISPLAY buttons for 2 seconds until the system emits a short beep, the program automatically exits and returns to Normal mode.

Smart-UPS C 1000/1500/2000/3000 VA 120/230 Vac Rack-Mount 2U

9

Image 11
Contents Smart-UPSC Page Product Description Safety MessagesSafety and General Information Specifications Product Overview Front panel featuresRear panel features  UPS input InstallationConnect equipment to the UPS OperationDisplay panel features Status IndicatorsSensitivity adjustment settings LCD status indicators LED status indicators120 Vac 230 Vac Description Display interface featuresConfiguration Mode Feature Reference GuideSystem Faults Normal ModeSensitivity SettingGreen Mode Function Options Description Self-TestProblem and Possible Cause Solution TroubleshootingTransport ServiceBattery Replacement Two Year Limited Factory Warranty Smart-UPS C 1000/1500/2000/3000 VA 120/230 Vac Rack-Mount 2U Page EN 990-4472C 12/2013 APC by Schneider Electric Worldwide Customer Support

SMC10002U, SMC15002U specifications

The APC SMC15002U and SMC10002U are rugged and reliable line interactive UPS (Uninterruptible Power Supply) systems designed to keep your critical electronic equipment operational during power disruptions. These UPS units are part of APC’s Smart-UPS family, renowned for their efficiency and effectiveness in protecting sensitive electronics in office and home environments.

One of the main features of both models is their ability to deliver pure sine wave output. This ensures that connected devices receive clean power, which is crucial for sensitive equipment like servers, networking hardware, and telecommunications systems. This feature significantly reduces the risk of damage or malfunction in sensitive electronics compared to standard modified sine wave UPS systems.

The SMC15002U offers a capacity of 1500 VA/900 W, while the SMC10002U provides 1000 VA/600 W. This flexibility allows users to select a model based on their specific power requirements, catering to various applications from small businesses to home offices. Both models incorporate Automatic Voltage Regulation (AVR) technology, which stabilizes voltage fluctuations by automatically adjusting the incoming voltage. This feature helps ensure that connected devices operate consistently and enhances their lifespan.

Battery management is another strong point of the SMC series. These UPS models utilize intelligent battery management systems that prolong battery life and provide notifications for battery replacement. The user-friendly LCD interface displays real-time information about the UPS's status, including battery capacity, load level, and input/output voltage levels, allowing for seamless monitoring.

Furthermore, the SMC15002U and SMC10002U include multiple outlets, providing ample connectivity for various devices. They also have a compact rack-mountable design, which is ideal for data centers and network closets where space is at a premium. The ability to integrate with network management systems through optional accessories allows for remote monitoring, enabling IT administrators to respond to power events swiftly.

In summary, the APC SMC15002U and SMC10002U are advanced UPS solutions that combine high-capacity power, pure sine wave output, AVR technology, and intelligent battery management to protect critical electronic equipment. Their robust features and reliability make them a valuable asset for anyone looking to safeguard their investments in technology against power interruptions.